Master Programming Level

Printer/PC

OPTION MODULES
1=ANNUNCIATORS/UDACT
2=ON BOARD DACT
A Printer or a PC can be connected to the control panel. Pressing 3 while viewing the Option
3=PRINTER/PC
NO
Module Screen will cause the following screen to appear:
Option Module Screen
Pressing 1 while viewing the Printer-PC Screen will program the control panel for an unsupervised
(NO SU) printer. The display will change to the Printer Baud Rate Screen as shown below.
Pressing 2 while viewing the Printer-PC Screen will program the control panel for a supervised
(SU) printer. Printer supervision, when enabled, will typically detect the removal of the printer
cable and will detect when the printer power has been turned off. Depending upon the brand of
printer, other errors such as paper empty or printer off-line may be detected.
The following screen will appear, which allows the programmer to select the baud rate for the
printer communication:
Pressing the number key corresponding to the desired baud rate (2 for 4800 Baud for example) will
program the control panel for the selected baud rate and return the display to the Option Module
Screen which will indicate Printer/PC PR4800 for a supervised printer installed at 4800 baud rate.
Pressing 3 while viewing the Printer-PC Screen will program the control panel for a PC connection.
The display will return to the Option Module Screen which will indicate Printer/PC PC for
personal computer installed.
NOTE: The LCD-80F and the Printer/PC use the same TB8 terminal block. Only one device can
be used at any one time. Setting any option in the Printer/PC screen to Yes will disable
communications with the LCD-80F. The printer must be installed in the same room and within 50
feet of the FACP.
3.6.10 Password Change
The factory set passwords, which have been programmed into the control panel, can be changed by
selecting the Password Change option. Pressing 1 while viewing Programming Screen #4 will
PROGRAMMING
1=PASSWORD CHANGE
cause the following screen to be displayed:
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
Press 1 to change the Master Programming Level password, 2 to change the Maintenance Level
password or 3 to change the Remote Download password. Note that the passwords will not be
displayed on LCD annunciators.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
PRINTER-PC
1=PRINTER NO SU
2=PRINTER SU
YES
3=PC
NO
Printer-PC Screen
PRINTER BAUD RATE
1=2400 BAUD
2=4800 BAUD
3=9600 BAUD
Printer Baud Rate Screen
PASSWORD CHANGE
1=MASTER
2=MAINTENANCE
3=REMOTE DOWNLOAD
Password Change Screen
NO
Programming
125