Programming
To enter the user Programming mode, press 2. The display will read as follows:
Entering the Master level password (default 00000) will cause the following screen to appear:
If the Maintenance level password (default 11111) is entered, the following screen will appear:
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.

3.6 Master Programming Level

When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and
the system Trouble LED flashes until Programming mode is exited. The following display will
appear:
The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the
display, pressing the 'down' arrow key will display the subsequent Programming Screens as
illustrated below while pressing the 'up' arrow key will display the previous screen.
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
3.6.1 Autoprogram
PROGRAMMING
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which

1=AUTOPROGRAM

2=POINT PROGRAM
prompts the control panel to poll all devices installed on the SLC loop. The primary purpose of
3=ZONE SETUP
autoprogramming is to allow the installer a fast and easy way to bring the system on-line as quickly
Programming Screen #1
as possible. The first time the system is powered-up, it should be autoprogrammed.
If the system is already programmed and Autoprogram is initiated, the system will only add default
values for newly installed devices.
66
PROGRAMMING
ENTER PASSWORD

PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Master Programming Level
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4