Installation of Optional Modules
MS-2/MS-4 PN 51512:D 10/18/04

2.6.2.2 4XZMF Zone Relay Module (MS-4 only)

The 4XZMF provides four zone alarm, one system alarm and one system trouble
Form-C relays. Nonpower-limited and power-limited wiring must have a minimum
distance of 0.25", wire to wire. If this module is used to drive nonpower-limited and
power-limited circuits, follow the instructions below:
Relay #1 through #4 will activate with Output #1 through
#4 and remain latched unless 'LATCH' jumper is cut.
Use Disable Switch to
disconnect the relays
Cut jumper for nonlatching
(silenceable) relay operation
1) Skip a set of dry contacts to maintain the 0.25" required space between power-
limited and nonpower-limited circuits. The wiring of this module must follow the
requirements as specified in "Power-limited Wiring Requirements" on page 24.
2) If this module is needed to drive power-limited and nonpower-limited relays that are
next to each other, refer to the following illustration which shows a typical connection:
{
NO
Relay #1
NC
C
{
NO
Relay #2
NC
C
{
NO
Relay #3
NC
C
{
NO
Relay #4
NC
C
Figure 2.14 4XZMF Zone Relay Module
}
1
NO
2
NC
Relay #1
3
C
}
4
NO
5
NC
Relay #2
6
C
}
7
NO
8
NC
Relay #3
9
C
}
10
NO
11
NC
Relay #4
12
C
}
13
NO
14
NC
Alarm
15
C
16
}
NO
17
NC
Trouble
18
C
OR
}
power-limited circuit
}
power-limited circuit
}
no connection
nonpower-limited circuit
}
nonpower-limited circuit
Installation
29