UL Power-limited Wiring Requirements
Power-limited Circuits (Class 2)
AC
Power
Grounding
Stud (see
Figure 2.5)
Wire Nut
Figure 2.12 Typical UL Power-limited Wiring Requirements
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Nonpower-limited Circuits
To
Batteries
Ground
Cable
#71073
Power-limited Circuits (Class 2)
Nonpower-limited Circuits
Installation
Power-limited
Circuits (Class 2)
maintain minimum
0.25" between
power-limited and
nonpower-limited
circuits wiring
Ferrite Clamps
(See Section 2.8.1
for for more
information.)
Nonpower-limited,
(Class 1) supervised
Telephone Circuit
37