Fire-Lite MS-9600 User Manual

Fire-Lite MS-9600 User Manual

Fire alarm control panel
Hide thumbs Also See for MS-9600:
Table of Contents

Advertisement

PN: 51335:E
ECN 03-352
Fire Alarm Control Panel
MS-9600/MS-9600E
IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this
manual when installing or servicing the Fire Alarm Control Panel.
E
Document
#51335
7/9/03
Revision:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MS-9600 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Fire-Lite MS-9600

  • Page 1 PN: 51335:E ECN 03-352 Fire Alarm Control Panel MS-9600/MS-9600E IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this manual when installing or servicing the Fire Alarm Control Panel. Document #51335 7/9/03 Revision:...
  • Page 2 While a fire alarm system may lower insurance Fire Alarm System Limitations rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke Heat detectors do not sense particles of combustion and alarm detectors, heat detectors, manual pull stations, audible warn- only when heat on their sensors increases at a predetermined ing devices, and a fire alarm control with remote notification...
  • Page 3: Installation Precautions

    Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may nected to the fire alarm control panel. Disconnect all sources operate erratically or can be damaged when subjected to light- of power before servicing.
  • Page 4 Notes MS-9600 PN 51335:E 7/9/03...
  • Page 5: Table Of Contents

    2.6.6.4 ACM and AFM Series Annunciators ..................42 SECTION 3: Programming ...........................43 3.1: Programming Data Entry ..........................43 3.2: User Programming ............................44 3.3: Initial Power-up............................45 3.4: Programming Screens Description......................45 3.5: Programming and Passwords ........................45 3.6: Master Programming Level.........................47 MS-9600 PN 51335:E 7/9/03...
  • Page 6 3.6.5.8 Waterflow Silenceable ......................94 3.6.6: Verify Loops ............................94 3.6.7: History ...............................95 3.6.7.1 View Events ..........................95 3.6.7.2 Erase History ...........................95 3.6.8: Walktest .............................96 3.6.9: Option Modules..........................97 3.6.9.1 Annunciators/UDACT ......................97 3.6.9.2 On Board DACT ........................98 3.6.9.3 Printer/PC ..........................98 MS-9600 PN 51335:E 7/9/03...
  • Page 7 4.22: Read Status ..............................123 4.22.1: System Point ...........................124 4.22.2: Zones ...............................125 4.22.3: Power...............................126 4.22.4: Trouble Reminder ...........................127 4.22.5: Timers..............................127 4.22.6: NAC ..............................128 4.22.7: Relays..............................128 4.22.8: Program Check..........................129 4.22.9: History.............................129 4.22.10: Annunciators ..........................130 4.22.11: Phone Line.............................130 4.22.12: Central Station..........................131 MS-9600 PN 51335:E 7/9/03...
  • Page 8 5.4: Calculating the Battery Size ........................139 5.4.1: NFPA Battery Requirements ......................139 5.4.2: Selecting and Locating Batteries.......................139 APPENDIX A: Software Zones ..........................140 A.1: Correlations ...............................140 APPENDIX B: Default Programming .........................148 APPENDIX C: NFPA Standard-Specific Requirements ...................149 APPENDIX D: Wire Requirements ........................156 MS-9600 PN 51335:E 7/9/03...
  • Page 9 411UDAC Communicator/Transmitter Document #51073 CHG-120F Battery Charger Document #50888 CHG-75 Battery Charger Document #51315 LDM Series Lamp Driver Modules Document #50055 LCD-80F Remote Fire Annunciator Document #51338 ACM-8RF Relay Control Module Document #50362 DACT-UD Manual Document #51899 MS-9600 PN 51335:E 7/9/03...
  • Page 10 MS-9600 PN 51335:E 7/9/03...
  • Page 11 TENS 16 HR DELAY ADDRESS TB 1 SW 1 GND FLT DISABLE ONES TB 3 TB 4 J2 J3 A- B- A+ B+ NC NO C CHG-75 Charger CHG-120F Charger Doc. # 51315 Doc. # 50888 MS-9600 PN 51335:E 7/9/03...
  • Page 12: Section 1: Product Description

    The MS-9600E offers the same features as the MS-9600 but allows connection to 220/240 VAC input. Note: Unless otherwise specified, the term MS-9600 is used in this manual to refer to both the MS-9600 and the MS-9600E FACPs.
  • Page 13 BG-10LX: Manual Pull Station • Optional 4XTMF module (conventional reverse polarity/city box transmitter) • Optional DACT-UD Digital Alarm Communicator Transmitter, reports up to 99 zones or 636 points (all devices) to a UL listed Central Station MS-9600 PN 51335:E 7/9/03...
  • Page 14: Specifications

    Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp Maximum Battery Charger Capacity: 25 Amp Hour (MS-9600 cabinet holds maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 75 Amp Hour batteries, use the CHG-75 Battery Charger and BB26 or BB-55F Battery Box.
  • Page 15: 1: Current Availability

    NAC # 2 3 amps max Style Y or Z per circuit NAC # 4 3 amps max Style Y only per circuit Refer to the battery calculations section for additional information. Figure 1.1 Current Availability MS-9600 PN 51335:E 7/9/03...
  • Page 16: Controls And Indicators

    • Escape key • Mode key • Four cursor keys (up, down, left and right) • Enter key Local Piezo Sounder A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions. MS-9600 PN 51335:E 7/9/03...
  • Page 17: Circuits

    Optional modules plug in and are mounted to the main circuit board. The circuit board is delivered in the MS-9600 kit and must be mounted to the backbox. Refer to the circuit board illustration on Page 10.
  • Page 18: 1: Intelligent Addressable Detectors: Newer Series

    The dress panel must be installed to meet FM requirements. Batteries The MS-9600 cabinet provides space for two batteries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour up to 25 Amp Hour require use of the Fire•Lite BB-26 or similar UL listed battery cabinet.
  • Page 19: 2: Intelligent Addressable Modules: Newer Series

    The BG-12LX is an addressable manual pull station featuring a key-lock reset. The pull station responds to an address set by the installer using the built-in rotary decimal switches on the pull station. The manual pull station includes a Fire•Lite key. MS-9600 PN 51335:E 7/9/03...
  • Page 20: 3: 300 Series Intelligent Addressable Devices

    1.6.3 300 Series Intelligent Addressable Devices Fire•Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9600 FACP. The devices must be configured for CLIP Mode operation if the control panel is installed in an existing system with 300 Series devices. The address of 300 Series devices cannot be set above 99.
  • Page 21: Accessories

    The PK-CD Programming Utility can be used to program an MS-9600 directly from most IBM compatible computers, including laptops and portables, equipped with a serial port. MS-9600 program files can also be created and stored on the PC and then downloaded to the control panel. The PK-CD Kit includes the MS-9600 Windows- based Programming Utility software on CD-ROM with on-line help file.
  • Page 22: 4: Battery Charger

    The ACM Series Annunciators remotely display alarm and trouble status as well as system status. In addition, they can provide remote Acknowledge, Silence, Reset and Drill functions. For more detailed information, refer to the appropriate annunciator manual. Following is a list of annunciators which can be used with the MS-9600. • ACM-16ATF...
  • Page 23: Getting Started

    Enter Autoprogramming (refer to "Autoprogram" on page 48) • Resolve Programming Conflicts • Go to Point Program to Enter Specific Data (refer to "Point Program" on page 49). Use the right and left arrow keys to navigate between devices. MS-9600 PN 51335:E 7/9/03...
  • Page 24: Section 2: Installation

    NEUT EARTH +BA TTERY - mounting studs mounting studs grounding stud: attach solid earth ground wire (refer to "AC Power and Earth MS-9600 Backbox Ground Connection" on page 27) Figure 2.1 MS-9600 Main Circuit Board Installation MS-9600 PN 51335:E 7/9/03...
  • Page 25 1.62“ 1.62“ 10.0“ 25.4 cm 47.0cm 18.5“ 4.45cm 1.75“ 17.35 cm 6.83“ 4.45cm 1.75“ 4.1cm 1.583“ 1.50“ 4.37“ 3.81 cm 11.1 cm 11.1 cm 4.37“ 1.50“ (3.81 cm) 1.75“ 4.45 cm Figure 2.2 MS-9600 Cabinet Mounting MS-9600 PN 51335:E 7/9/03...
  • Page 26 (47.3 cm) Depth = 4.75" 15.625" (12.07 cm) (39.688 cm) 21.620" 18.625" (54.92 cm) (47.308 cm) Battery Box = 8.5" (21.59 cm) Battery Box = 14.34" (36.42 cm) Trim Ring P/N:FC-TR Figure 2.3 MS-9600 Cabinet Dimensions MS-9600 PN 51335:E 7/9/03...
  • Page 27: Power

    2.2.1 AC Power and Earth Ground Connection Primary power required for the FACP is 120 VAC, 50/60 Hz, 3.2 amps for the MS-9600 or 220/240 VAC, 50/60 Hz, 1.6 LCD DISPLAY amps for the MS-9600E. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes.
  • Page 28: Relays

    The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the MS-9600 main circuit board. The NACs are configured for Style Y (Class B) from the factory. Refer to "Configuring NACs" on...
  • Page 29: 1: Configuring Nacs

    It is keyed to prevent incorrect insertion. Top edge of MS-9600 If the 4XTMF Option Module is to be installed in connectors Main Circuit Board...
  • Page 30: 3: Style Z (Class A) Nac Wiring

    2 Style Z (Class A) Notification Appliance Circuits, supervised and power-limited Polarized Bell Polarized Bell Polarized Strobe Polarized Strobe Polarized Horn Polarized Horn NAC 2 NAC 1 Notification Appliance Circuit polarity shown in alarm state Figure 2.8 NAC Style Z (Class A) Wiring MS-9600 PN 51335:E 7/9/03...
  • Page 31: Ul Power-Limited Wiring Requirements

    All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-9600 is shown below. 4XTMF SLC-2 UDACT-F Figure 2.9 Typical UL Power-limited Wiring Requirements...
  • Page 32: Optional Modules And Devices

    ACK/STEP DISABLE EVENT ALARM SILENCE OPT DACT OPT SLC CUT TO ENTER MONITOR 4XTM DRILL HOLD 2 SEC LCD DISPLAY MODE KEYPAD I/F RESET RECALL NEUT EARTH +BATTERY- Mounting Screw Access Holes Figure 2.10 Keypad/Display Removal MS-9600 PN 51335:E 7/9/03...
  • Page 33: 1: Dact-Ud Installation

    (3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.) 3 Touchtone Types: 4+1 Ademco Express 4+2 Ademco Express Ademco Contact ID The DACT-UD module plugs into connector J2 on the MS-9600 main circuit board. Primary Phone Line Secondary Phone Line Secondary Active LED Primary Active LED...
  • Page 34 3. Carefully plug connector J1 on back of the DACT-UD module into connector J2 on the MS-9600 main circuit board, being careful not to bend any pins 4. Align the mounting holes in the DACT module with the premounted standoffs on...
  • Page 35 Secondary Phone Line PH-1 (MCBL-7) order separately Male Plug Connectors CAUTION: It is critical that the DACT-UD be located as the first device on the incoming Female telephone circuit to properly function Connectors DACT-UD Figure 2.14 Wiring Phone Jacks MS-9600 PN 51335:E 7/9/03...
  • Page 36: 2: 4Xtmf Transmitter Module Installation

    Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the MS-9600. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.
  • Page 37: 3: Auxiliary Trouble Input (J16 & J17)

    +BATTERY- Figure 2.16 4XTMF Connectors to MS-9600 Connectors NOTE: Jumper JP5 on the MS-9600 main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module. The supervisory relay must be programmed as shown on the main circuit board silkscreen (TB5, Terminals 7, 8 & 9).
  • Page 38: 4: Slc-2 Expander Module

    Optional Modules and Devices 2.6.4 SLC-2 Expander Module The optional SLC-2 Expander Module provides a second SLC loop for the MS-9600 control panel. This allows connection of an additional 318 addressable devices, bringing the total to 636 addressable devices which can be connected to the FACP.
  • Page 39: 5: Printer/Pc

    Installation of either device requires panel programming to allow the FACP to communicate with the device. CAUTION! Do not connect a printer or PC to the MS-9600 FACP if a ground fault exists on the control panel. Circuit damage may result. Remove all power (AC and DC) before installing or removing any wiring.
  • Page 40: 6: Digital Communicator And Annunciators

    The optional BRKT-9600 Universal Bracket can be used to mount specific modules inside the MS-9600 cabinet. The BRKT-9600 mounts to two studs located in the lower right corner of the control panel cabinet as illustrated below. It is secured to the PEM studs on the back wall of the cabinet with two supplied hex nuts.
  • Page 41 Optional Modules and Devices Installation Module Installation on BRKT-9600 The following modules can be installed inside the MS-9600 cabinet using the BRKT-9600 Universal Bracket: UDACT-F Digital Alarm Communicator/Transmitter - installs at standoff location (A) ACM-8RF Annunciator Control Module (Relay) - installs at standoff location Refer to the appropriate module manual for detailed information on module operation and wiring.
  • Page 42: Acm And Afm Series Annunciators

    Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159 not used Important: If a UDACT-F is installed in the MS-9600 and selected in programming, the control panel will automatically assign annunciator addresses 20 - 31 to the UDACT-F and disable the selection of these addresses in programming for ACM annunciators.
  • Page 43: Section 3: Programming

    The keyboard can be connected to the PS-2 connector J7 on the control panel main circuit board. The information presented in this section refers to programming the MS-9600 via the onboard keypad. If an optional computer keyboard is connected to the MS-9600 main circuit board, the following table describes the keyboard keys which correspond to the onboard keypad keys.
  • Page 44: User Programming

    Programming User Programming 3.2 User Programming The MS-9600 is completely field programmable and requires no special software skills. While programming the MS-9600, the fire protection capabilities of the control panel ! ! ! are enabled. Site-specific programming may be accomplished in three ways: •...
  • Page 45: Initial Power-Up

    ESC key in order to store the program data entered during this mode. If the Reset key is pressed or power is lost before exiting Programming mode, the data just entered will not be saved. MS-9600 PN 51335:E 7/9/03...
  • Page 46 If the Maintenance level password (default 11111) is entered, the following screen will appear: PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key. MS-9600 PN 51335:E 7/9/03...
  • Page 47: Master Programming Level

    Programming Screens as illustrated below while pressing the ‘up’ arrow key will display the previous screen. PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOPS Programming Screen #2 PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES Programming Screen #3 PROGRAMMING 1=PASSWORD CHANGE 2=CLEAR PROGRAM 3=PROGRAM CHECK Programming Screen #4 MS-9600 PN 51335:E 7/9/03...
  • Page 48: 1: Autoprogram

    Autoprogram Result Screen #2 In the preceding example, the first display indicates that Loop 1 has 55 addressable detectors, 35 monitor modules and 30 control modules installed. The second display indicates that Loop 2 has no devices installed. MS-9600 PN 51335:E 7/9/03...
  • Page 49: 2: Point Program

    ADD DETECTOR ENTER DETECTOR# Add Detector Screen A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 005. MS-9600 PN 51335:E 7/9/03...
  • Page 50: Delete Detector

    3 in the Detector Screen. The following screen will be displayed: EDIT DETECTOR ENTER POINT ADDRESS Edit Detector Screen A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 017. MS-9600 PN 51335:E 7/9/03...
  • Page 51 V or * - indicates whether or not alarm verification is enabled (V = alarm verification enabled and * = alarm verification disabled) 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop 1, D=Detector and 017 = Detector Address 017) MS-9600 PN 51335:E 7/9/03...
  • Page 52 The control panel will display the device type and address which has been disabled and Edit Detector Screen #2 will turn on the Trouble LED and Disable LED. MS-9600 PN 51335:E 7/9/03...
  • Page 53 3 minutes. Zone 97, however, will activate immediately and may be used to connect a signaling device to indicate PAS activation (do not use a Notification Appliance Circuit for this purpose). MS-9600 PN 51335:E 7/9/03...
  • Page 54 Z98 will cause its associated control module to activate immediately, sounding the connected signaling device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition. MS-9600 PN 51335:E 7/9/03...
  • Page 55 Pressing 1 while viewing Edit 1=NOUN/ADJECTIVE Detector Screen #5 will cause the following screen to be displayed: 2=DESCRIPTION ***************** Edit Detector Screen #5 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9600 PN 51335:E 7/9/03...
  • Page 56 Adjective Screen #1 ********************** ********************** 1=FLOOR1 1=WEST 2=FLOOR2 2=FRONT 3=FLOOR3 3=CENTER Adjective Screen #6 Adjective Screen #2 ********************** ********************** 1=REAR 1=FLOOR4 2=UPPER 2=FLOOR5 3=LOWER 3=ROOM Adjective Screen #3 Adjective Screen #7 ********************* 1=MAIN 2=FIRST 3=2ND Adjective Screen #4 MS-9600 PN 51335:E 7/9/03...
  • Page 57 3=ELECTRIC RM 3=ROOM Noun Screen #2 Noun Screen #6 ********************** ********************** 1=ELEVATOR 1=STAIRWAY 2=ENTRANCE 2=STOREROOM 3=FLOOR 3=WING Noun Screen #3 Noun Screen #7 ********************** ********************** 1=GARAGE 1=ZONE 2=HALLWAY 3=HVAC RM Noun Screen #4 Noun Screen #8 MS-9600 PN 51335:E 7/9/03...
  • Page 58 0. If the last character goes from 9 to 0 and the characters to the left of the last character are also numbers, they are also incremented (overflow) • The above increment function may be repeated with each press of the zero key MS-9600 PN 51335:E 7/9/03...
  • Page 59: Module Programming

    ADD MODULE ENTER MODULE# Add Module Screen #1 A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 005. MS-9600 PN 51335:E 7/9/03...
  • Page 60: Delete Module

    A flashing cursor will appear in the position of the first asterisk to the left. Using the panel keypad, key in the module address such as 005. When the last digit is keyed in, the following confirmation that the module has been deleted will be displayed: DELETE MODULE MODULE# IS DELETED MS-9600 PN 51335:E 7/9/03...
  • Page 61: Edit Module Screen For Monitor Module

    ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the two digit zone number from 000 - 099) 1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module and 012 = Module Address 012) MS-9600 PN 51335:E 7/9/03...
  • Page 62 Yes and Enabled No. If Enabled No is selected, the module will not be polled by the control panel, preventing the module from reporting alarms and troubles to the panel. The control panel will indicate a system trouble condition and the Disable LED with turn on if any devices are disabled. MS-9600 PN 51335:E 7/9/03...
  • Page 63 The display will return to the Edit Monitor Screen #2 which will show the new type selection. The Table 3.1 on page 64 lists the Monitor Types and their respective functions. MS-9600 PN 51335:E 7/9/03...
  • Page 64 Acts like panel Acknowledge Key Sil-Switch Acts like panel Silence Key Reset-Switch Acts like panel Reset Key Drill-Switch Acts like panel Drill Key PAS-Bypass PAS Disable Future not used Note: For the PROCESS-MONITOR-AR selection, AR refers to AutoResettable MS-9600 PN 51335:E 7/9/03...
  • Page 65 Pressing 1 while viewing ***************** Edit Monitor Screen #5 will cause the following screen to be displayed: Edit Monitor Screen #5 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9600 PN 51335:E 7/9/03...
  • Page 66 1=WEST 2=FLOOR 2 2=FRONT 3=FLOOR 3 3=CENTER Adjective Screen #6 Adjective Screen #2 ********************** ********************** 1=REAR 1=FLOOR 4 2=UPPER 2=FLOOR 5 3=LOWER 3=ROOM Adjective Screen #3 Adjective Screen #7 ********************** 1=MAIN 2=FIRST 3=2ND Adjective Screen #4 MS-9600 PN 51335:E 7/9/03...
  • Page 67 Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK-CD programming kit. MS-9600 PN 51335:E 7/9/03...
  • Page 68 0. If the last character goes from 9 to 0 and the characters to the left of the last character are also numbers, they are also incremented (overflow) • The above increment function may be repeated with each press of the zero key MS-9600 PN 51335:E 7/9/03...
  • Page 69: Edit Module Screen For Control Modules

    ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number from 000 - 099) 1M002 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module and 002 = Module Address 02) MS-9600 PN 51335:E 7/9/03...
  • Page 70 Yes and Enabled No. If Enabled No is selected, the module will not be polled by the Edit Control Screen #2 control panel, preventing the module from activating its output devices. The control panel will indicate a system trouble condition and the Disable LED will turn on if any devices are disabled. MS-9600 PN 51335:E 7/9/03...
  • Page 71 The following table contains control module type codes and their functions: Control Type Special Function Future Use None Bell Circuit None Horn Circuit None Sounders None Relay Ignore Open Circuit Strobe Circuit None Control None Resettable Power None Future Use None MS-9600 PN 51335:E 7/9/03...
  • Page 72: Zone Assignment

    Pressing 1 while viewing Edit Control Screen #4 will cause the following screen to be displayed: Edit Control Screen #4 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9600 PN 51335:E 7/9/03...
  • Page 73 1=WEST 2=FLOOR 2 2=FRONT 3=FLOOR 3 3=CENTER Adjective Screen #6 Adjective Screen #2 ********************** ********************** 1=REAR 1=FLOOR 4 2=UPPER 2=FLOOR 5 3=LOWER 3=ROOM Adjective Screen #3 Adjective Screen #7 ********************** 1=MAIN 2=FIRST 3=2ND Adjective Screen #4 MS-9600 PN 51335:E 7/9/03...
  • Page 74 Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK-CD programming kit. MS-9600 PN 51335:E 7/9/03...
  • Page 75 4. Press the right arrow key to advance the zone field 5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones MS-9600 PN 51335:E 7/9/03...
  • Page 76: 3=Zone Setup

    Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z. Another zone can then be enabled. MS-9600 PN 51335:E 7/9/03...
  • Page 77: Disable

    Pre-signal condition in the control panel. Do not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal condition. Zone 99, in special purpose mode, is reserved for future use and has no effect. MS-9600 PN 51335:E 7/9/03...
  • Page 78: Zones Installed

    Press the up or down arrow keys to view the additional zones. MS-9600 PN 51335:E 7/9/03...
  • Page 79: Zone Type

    Waterflow silenceable zone type to the selected zone. Any signaling devices programmed to the same zone can be silenced by pressing the Alarm Silence key or by using the auto-silence feature. To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page MS-9600 PN 51335:E 7/9/03...
  • Page 80: 4: Loop Setup

    Screen will have no effect on programming at this time. Device Addressing It is important to note that the MS-9600 addressable device capacity is 159 detectors and 159 control/monitor modules per SLC loop. Since older legacy addressable devices cannot be set to addresses above 099, the newer series devices must be used when addresses 100 to 159 are to be installed.
  • Page 81: 5: System Setup

    3=VERIFY LOOPS Programming Screen #2 SYSTEM SETUP 1=TROUBLE REM 2=BANNER 3=TIME-DATE System Setup Screen #1 SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS System Setup Screen #2 SYSTEM SETUP 1=CANADIAN OPT. 2=WATERFLOW SIL. System Setup Screen #3 MS-9600 PN 51335:E 7/9/03...
  • Page 82: Trouble Reminder

    Pressing 2 while viewing the Banner Screen will display the following screens : USER DEFINED BANNER PRESS ENTER IF OK User Defined Banner Screen #1 USER BANNER - LINE 2 PRESS ENTER IF OK ************ User Defined Banner Screen #2 MS-9600 PN 51335:E 7/9/03...
  • Page 83: Time-Date

    At this point enter 1 for AM or 2 for PM. The display will then return to the Time-Date Screen which will show the new time entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and beginning again. MS-9600 PN 51335:E 7/9/03...
  • Page 84: Date

    Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the programmer to select the month that daylight savings time will begin. In this sub-screen, pressing 1 will select March, 2 will select April and 3 will select May. MS-9600 PN 51335:E 7/9/03...
  • Page 85: Timers

    005 for five seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time. MS-9600 PN 51335:E 7/9/03...
  • Page 86: Presignal Delay

    25 for twenty-five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time. MS-9600 PN 51335:E 7/9/03...
  • Page 87: Ac Loss Delay

    NAC 1, 2 for NAC 2, 3 for NAC 3 or 4 for NAC 4. Note that 3=NAC 3 and 4=NAC 4 will only be displayed if the NACKEY NAC option card is installed, in JP8 of the main circuit board, for Class B operation. MS-9600 PN 51335:E 7/9/03...
  • Page 88: Enabled

    Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No. MS-9600 PN 51335:E 7/9/03...
  • Page 89: Type

    Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the synchronization feature is selected, only the audible devices will be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to operate. MS-9600 PN 51335:E 7/9/03...
  • Page 90: Auto Silence

    Pressing 2 while viewing NAC Screen #2 will cause the following displays to appear: CODING 1=STEADY 2=MARCH TIME 3=CALIFORNIA Coding Screen #1 CODING 1=TEMPORAL 2=TWO STAGE Coding Screen #2 MS-9600 PN 51335:E 7/9/03...
  • Page 91 Zone 99 or if the timer counts down to zero 8. Control modules that are programmed to the same zone as the activated input device will not be delayed for activation MS-9600 PN 51335:E 7/9/03...
  • Page 92: Zone

    Screen #4 will cause the following screen to be displayed: NAC Screen #4 NAC SYNC TYPE 1=SYSTEM SENSOR 2=WHEELOCK 3=GENTEX Pressing 1 while viewing this screen will select System Sensor synchronization, 2 will select Wheelock and 3 will select Gentex. MS-9600 PN 51335:E 7/9/03...
  • Page 93: Relays

    If the corresponding condition is cleared, the relay will return to its normal state without the necessity of resetting the control panel. MS-9600 PN 51335:E 7/9/03...
  • Page 94: Canadian Option

    When Loop verification has been completed, the display will indicate that the system is OK or, if problems have been detected, any device type programming errors. Use the up and down arrow keys to view all detected errors. MS-9600 PN 51335:E 7/9/03...
  • Page 95: 7: History

    Pressing 1 while viewing the Erase History Screen will erase all events from the History file. During this process, the display will read as follows: ERASING HISTORY PLEASE WAIT Erase History Wait Screen After the History file has been erased, the display will return to the History Screen. MS-9600 PN 51335:E 7/9/03...
  • Page 96: 8: Walktest

    Note that the Walktest log is stored in RAM. If all power (AC and DC) is removed from the FACP, the Walktest log information will be lost. This information is also overwritten when subsequent walktests are performed. MS-9600 PN 51335:E 7/9/03...
  • Page 97: 9: Option Modules

    A Terminal Mode annunciator , ACS Mode annunciator and remote UDACT can be installed in the MS-9600 system. To enable any of these devices, press the number corresponding to the selected device shown in Annunciator Screen #1 so that Yes appears in the display to the right of the device.
  • Page 98: On Board Dact

    Enabling either printer option will cause the following screen to appear, which allows the programmer to select the baud rate for the printer communication: PRINTER BAUD RATE 1=2400 BAUD 2=4800 BAUD 3=9600 BAUD Printer Baud Rate Screen MS-9600 PN 51335:E 7/9/03...
  • Page 99: 10: Password Change

    NEW MASTER PASSWORD IS 10101 PRESS ENTER IF OK Password Change Screen Pressing the Enter key will program the new password into the control panel and return the display to the Password Change Screen. MS-9600 PN 51335:E 7/9/03...
  • Page 100: 11: Clear Program

    WARNING! SYSTEM CHANGE PROCEED? 1=YES 2=NO Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will prevent programming from being cleared. MS-9600 PN 51335:E 7/9/03...
  • Page 101: 12: Program Check

    Note: If the NACs have been configured for Class A in the Setup option, only NAC1 and NAC2 will display test information. NAC 3 and NAC 4 will display asterisks (*) and will not be included in the test. MS-9600 PN 51335:E 7/9/03...
  • Page 102 001 on loop 1 but have not been programmed to any output devices. Use the up and down arrow keys to view all the zones without output assignments. MS-9600 PN 51335:E 7/9/03...
  • Page 103: Maintenance Programming Level

    Note that in the preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key, as shown in the following screen. PROGRAMMING 1=WALKTEST 2=SYSTEM 3=ZONE SETUP MS-9600 PN 51335:E 7/9/03...
  • Page 104: 1: Disable Point

    EDIT DETECTOR 1D001 1=ENABLED Enable/Disable Select Screen Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled MS-9600 PN 51335:E 7/9/03...
  • Page 105: 2=History

    Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY, PLEASE WAIT to be displayed. The display will then return to the History Screen. Pressing 2 will cause the display to return to the History Screen without erasing the History file. MS-9600 PN 51335:E 7/9/03...
  • Page 106: 3=Program Check

    (control module in this example) with an address of 001 on loop 1 but have not been programmed to any input devices. Use the up and down arrow keys to view all the zones without input assignments. MS-9600 PN 51335:E 7/9/03...
  • Page 107: 4: Walktest

    Pressing 3 after the walktest has been completed, will allow the operator to view the results of the walktest. 3.7.5 System To program the time and date into the control panel, press 2 while viewing Maintenance Screen #2. The following display will appear: SYSTEMS 1=TIME/DATE System Screen MS-9600 PN 51335:E 7/9/03...
  • Page 108: Time And Date

    The cursor will move one position to the right after each entry. When the fourth digit of the year has been entered, the display will return to the Time and Date Screen which will show the new date. MS-9600 PN 51335:E 7/9/03...
  • Page 109: 6: Zone Setup

    (00 - 99). After the second digit is entered, the zone will be disabled and the cursor will return to the original position. The next zone to be disabled can then be entered. Press Esc (Escape) to return to the previous screen. MS-9600 PN 51335:E 7/9/03...
  • Page 110 Pre-signal condition in the control panel. Do not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal condition. Zone 99, in special purpose mode, is reserved for future use and has no effect. MS-9600 PN 51335:E 7/9/03...
  • Page 111: Section 4: Operating Instructions

    It also performs a lamp test by turning on all LEDs (except the Ground LED), piezo sounder and LCD display segments after the Reset key is released. Any alarm or trouble that exists after a reset will resound the system. MS-9600 PN 51335:E 7/9/03...
  • Page 112: Led Indicators

    Battery This is a yellow LED that flashes to indicate a low battery voltage condition. Ground This is a yellow LED that turns on steady to indicate a ground fault condition. MS-9600 PN 51335:E 7/9/03...
  • Page 113: Normal Operation

    FIRE-LITE ALARMS INC SYSTEM ALL NORMAL 10:00A 010801 The MS-9600 performs the following functions at regular intervals while in Normal mode: Monitors AC input voltage and battery voltage Monitors and reports status of SLC loop(s), option cards and control panel Polls all devices on the SLC loop(s) and flashes each device LED while checking for valid replies, alarms, troubles, etc.
  • Page 114 Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of the month and 01 for the year 2001 Device Address; 1D001 in this example 1 represents SLC Loop1, D represents a detector and 001 represents device address 001 MS-9600 PN 51335:E 7/9/03...
  • Page 115: Alarm Operation

    Refer to "Edit Detector" on page 50, "Edit Module Screen for Monitor Module" on page 61 and "Edit Module Screen for Control Modules" on page 69 for information on additional device types. MS-9600 PN 51335:E 7/9/03...
  • Page 116: Supervisory Operation

    Open circuits in supervisory wiring are processed by the control panel the same way as other trouble conditions. Refer to "Alarm Operation" on page 115, for a description of the information displayed on the control panel LCD. MS-9600 PN 51335:E 7/9/03...
  • Page 117: Process Monitor Operation

    When an input device alarms and is not disabled, it activates all software zones assigned to it. An output device that is not disabled is turned on when any of the software zones to which it is programmed become active. MS-9600 PN 51335:E 7/9/03...
  • Page 118: Disable/Enable Operation

    4.14 Time Functions: Real-Time Clock The MS-9600 includes a crystal-based clock that provides time of day, date and day of week. Time is displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time change-over is programmable and automatic. If both AC and battery are lost, the time must be reset.
  • Page 119: Synchronized Nac Operation

    Presignal does not affect monitor modules programmed as waterflow, supervisory, process monitoring or remote switches. Presignal operation requires the approval of the local Authority Having Jurisdiction. MS-9600 PN 51335:E 7/9/03...
  • Page 120: Positive Alarm Sequence

    This feature may be employed by wiring a normally open device, such as a switch, to a monitor module which has been programmed for PAS BYPASS. MS-9600 PN 51335:E 7/9/03...
  • Page 121: Special System Timers

    If selected, this option will delay the activation of a waterflow type alarm for a programmable time duration from 1 to 90 seconds. This delay is in addition to any time delay inherent in the waterflow device. This feature requires the approval of the local Authority Having Jurisdiction. MS-9600 PN 51335:E 7/9/03...
  • Page 122: 5: Alarm Verification

    NACs and control modules programmed for Walktest, then shut them off after eight seconds. While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change operations). The alarm relay is not activated. MS-9600 PN 51335:E 7/9/03...
  • Page 123: Read Status

    READ STATUS READ STATUS 1=TROUBLE REMINDER 1=SERVICE TERMINAL 2=TIMERS 2=PRINTER/PC 3=NACS 3=PRINT Read Status Screen #2 Read Status Screen #5 READ STATUS READ STATUS 1=RELAYS 1=TIME-DATE 2=PROGRAM CHECK 3=HISTORY Read Status Screen #3 Read Status Screen #6 MS-9600 PN 51335:E 7/9/03...
  • Page 124: 1: System Point

    (could also be ION for ionization smoke detector) • NORTH CLASSROOM - the Adjective/Noun label for this device • Z005 - the first of five possible assigned software zones • 1D001 - 1 = Loop 1, D = Detector, 001 = Address 001 MS-9600 PN 51335:E 7/9/03...
  • Page 125: 2=Zones

    Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98 reserved for Pre-signal and 99 reserved for future use • Zone Type - the Type assigned to each installed zone (default is Alarm) MS-9600 PN 51335:E 7/9/03...
  • Page 126 Normal 21.25 to 27.50 VDC 24V Nonresettable Normal 21.25 to 27.50 VDC Charger Normal 27.05 to 28.15 VDC Normal -1.3 to -1.6 VDC NACs Open Circuit -2.3 to -2.5 VDC Short Circuit 0 to 1.0 VDC MS-9600 PN 51335:E 7/9/03...
  • Page 127: 4: Trouble Reminder

    Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be displayed: TIMERS PAS DELAY PRE SIGNAL WATERFLOW TIMERS AC LOSS DELAY These screens indicate the delay time, in seconds, for each of four possible delay options. MS-9600 PN 51335:E 7/9/03...
  • Page 128: 6: Nac

    Pressing 1 while viewing Read Status Screen #3 will display the following screen: 1=RELAYS 2=PROGRAM CHECK 3=HISTORY Read Status Screen #3 RELAYS 1=RELAY 1 2=RELAY 2 3=RELAY 3 The operator can view the programmed option for each relay by pressing the corresponding number key. MS-9600 PN 51335:E 7/9/03...
  • Page 129: 8: Program Check

    1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS The operator can view all events which have been stored in the history file, only alarms or other events, such as troubles or supervisories, by pressing the corresponding number key. MS-9600 PN 51335:E 7/9/03...
  • Page 130: 10: Annunciators

    Pressing 2 while viewing Read Status Screen #4 will display the following screen: PHONE LINE PRIMARY TOUCHTONE SECONDARY TOUCHTONE This screen indicates the both the Primary and Secondary phone lines have been configured for touchtone dialing operation. MS-9600 PN 51335:E 7/9/03...
  • Page 131: 12: Central Station

    Central Station Screen #2 provides information on the Primary and Secondary Central Station programming which includes: • Test Time Interval • Account Code • 24 Hour Test Time • Phone Number • Communication Format • Event Codes MS-9600 PN 51335:E 7/9/03...
  • Page 132: 13: Service Terminal

    The display will inform the operator as to whether the control panel is configured for a printer or a PC. In the example above, PR4800 indicates that the panel is configured for a printer with a baud rate of 4,800. MS-9600 PN 51335:E 7/9/03...
  • Page 133: 15: Print

    If the addressable smoke detector’s Chamber reading is not within the acceptable range, clean the detector and check the Chamber value again. If the reading is still not within the acceptable range, immediately replace the detector. MS-9600 PN 51335:E 7/9/03...
  • Page 134 Dust accumulation above the allowed limit. DIRTY2 Table 4.1 Maintenance Alert Levels Figure 4.1 illustrates a graphic representation of the maintenance levels: DIRTY Maintenance Urgent Maintenance Alert Acceptable Range Low Chamber Reading VALUE Figure 4.1 Diagram of Maintenance Levels MS-9600 PN 51335:E 7/9/03...
  • Page 135: 16: Time-Date

    Pressing 1 while viewing Read Status Screen #6 will display the following screens: Read Status Screen #6 DAYLIGHT SAVINGS ENABLED START MONTH START WEEK WEEK-1 DAYLIGHT SAVINGS END MONTH END WEEK LAST-W MS-9600 PN 51335:E 7/9/03...
  • Page 136: Section 5: Power Supply Calculations

    Use Table 5.1 , to determine the total amount of current, in AC amperes (A), that must be supplied to the system. Table 5.1 AC Branch Circuit Requirements Number of Current Draw Total Current Device Type Devices (AC amps) per Device MS-9600 MS-9600E CHG-120F Sum Column for AC Branch Current Required MS-9600 PN 51335:E 7/9/03...
  • Page 137: Calculating The System Current Draw

    Use Table 5.3 on page 138 to calculate current draws as follows: 1. Enter the quantity of devices in all three columns 2. Enter the current draw where required. Refer to the Fire-Lite Device Compatibility Document for compatible devices and their current draw 3.
  • Page 138 Terminals 3 & 4, 5 & 6) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified. Current limitations of TB3 circuits is 3.0 amps per output 11.Total current draw listed above cannot exceed 7.0 amps in alarm. MS-9600 PN 51335:E 7/9/03...
  • Page 139: Calculating The Battery Size

    7 AH to 25 AH range. The control panel cabinet is capable of housing batteries up to 18 AH. Batteries larger than 18 AH require the BB-26, BB-55F or other UL listed external battery cabinet. MS-9600 PN 51335:E 7/9/03...
  • Page 140: Appendix A: Software Zones

    MMF-302 control module with address 04 CMF-300 control modules with addresses 09, 11 and 12 The example points out some of the key assignment features of the MS-9600. Addresses of detectors are not duplicated. Addresses of monitor and control modules are not duplicated. The control module with address 09 is assigned to three software zones (providing floor above and floor below).
  • Page 141 MMF-302 CMF-300 CP350 ZONE CMF-300 CP300 SD350 CMF-300 SD350 ZONE SD350 CMF-300 MMF-302 The zone correlations which are shown graphically above are also presented in Table A.1 on page 142 and Table A.2 on page 143. MS-9600 PN 51335:E 7/9/03...
  • Page 142 Table A.1 Detector Programming Sheet Example DETECTOR ZONE ASSIGNMENT Address Device Zone ADJ/NOUN Address Device Zone ADJ/NOUN Type Number Type Number SD350 FIRST HALL SD350 ELEV. LOBBY CP350 2ND FLOOR CP350 ROOM 210 SD350 3RD FLOOR SD350 MEZZANINE SD350 MECH. ROOM MS-9600 PN 51335:E 7/9/03...
  • Page 143 MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Zone ADJ/ Address Device Zone ADJ/NOUN Type Number NOUN Type Number MMF-300 MMF-302 1, 2 MMF-302 1, 2 MMF-302 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 1, 2, 3 CMF-300 CMF-300 CMF-300 CMF-300 MS-9600 PN 51335:E 7/9/03...
  • Page 144 Software Zones Correlations Table A.3 Blank Detector Programming Sheet - 1 of 2 DETECTOR ZONE ASSIGNMENT Address Device Zone ADJ/ Address Device Zone ADJ/NOUN Type Number NOUN Type Number MS-9600 PN 51335:E 7/9/03...
  • Page 145 Correlations Software Zones Table A.4 Blank Detector Programming Sheet - 2 of 2 DETECTOR ZONE ASSIGNMENT Address Device Zone ADJ/ Address Device Zone ADJ/NOUN Type Number NOUN Type Number MS-9600 PN 51335:E 7/9/03...
  • Page 146 Software Zones Correlations Table A.5 Blank Module Programming Sheet - 1 of 2 MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Zone ADJ/ Address Device Zone ADJ/NOUN Type Number NOUN Type Number MS-9600 PN 51335:E 7/9/03...
  • Page 147 Correlations Software Zones Table A.6 Blank Module Programming Sheet - 2 of 2 MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Zone ADJ/ Address Device Zone ADJ/NOUN Type Number NOUN Type Number MS-9600 PN 51335:E 7/9/03...
  • Page 148: Appendix B: Default Programming

    Loop 1 & 2 Protocol CLIP UDACT Trouble Reminder ACS Installed Banner Fire•Lite Printer-PC Time Format 12 Hr Printer Baud 9600 Hours Setting Canadian Option Minutes Setting Waterflow Silenceable Second Settings (future) AM-PM Setting Month Setting Day Setting Year Setting MS-9600 PN 51335:E 7/9/03...
  • Page 149: Appendix C: Nfpa Standard-Specific Requirements

    NFPA Standard-Specific Requirements NFPA Standard-Specific Requirements APPENDIX C The Fire•Lite MS-9600 has been designed for use in commercial, industrial and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appendix. The minimum...
  • Page 150 Remote Station The following figure illustrates an example of Central Station/Remote Station Reporting using a 411UDAC. The relay contacts from the MS-9600 may be used to trip any dialer UL listed for Central Station/Remote Station Services. The UDACT-F may also be used. Refer to Figure C.2, “Central Station Service Using UDACT-F,” on page 151.
  • Page 151 UDACT-F (Universal Digital Alarm Communicator/Transmitter). The UDACT-F transmits system status to UL listed Central Station receivers via the public switched telephone network. It may be mounted inside the MS-9600 cabinet using the BRKT-9600 mounting bracket or remotely in a UBS-1F or ABS-8RF enclosure.
  • Page 152 Correlations The following figure illustrates an example of Central Station/Remote Station Reporting using a 411UD. The relay contacts from the MS-9600 may be used to trip any dialer UL listed for Central Station/Remote Station Reporting Services. Note: The Monitor Module input, which is being used to monitor the 411UD Relay #2 Output (programmed for DACT Trouble), must be programmed as ‘Trouble’...
  • Page 153 Notes: 1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box. 2. Cut JP6 on the MS-9600 main circuit board to supervise placement of 4XTMF module and circuit. 3. Cut JP5 on the MS-9600 main circuit board to enable FACP Supervisory relay.
  • Page 154 Correlations NFPA 72 Remote Station Protective Signaling System Notes: 1. Cut Jumper JP6 on the MS-9600 main circuit board to supervise placement of the 4XTMF module. 2. Refer to "4XTMF Transmitter Module Installation" on page 36 for detailed information. Fire•Lite RS82 Remote Station Receiver UL listed.
  • Page 155 Trouble condition. Form-C relay contact programmed to activate on Supervisory condition. Notes: 1. Connection between the MS-9600 and the transmitter are supervised by the transmitter. 2. This MS-9600/Transmitter arrangement can be employed for NFPA 72 Proprietary Protective Signaling System.
  • Page 156: Appendix D: Wire Requirements

    Connecting external system accessories to the MS-9600 main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, wire gauge and wire run length for each MS-9600 circuit. Reference the chart below to specify wire requirements and limitations for each MS-9600 circuit.
  • Page 157 AEM-32AF Annunciator 22 Calculating the Battery Size 139 installation 33 AFM annunciator 42 Canadian Option 81, 94 see also Digital Alarm Commu- AFM-16AF Annunciator 22 Central Station/Remote Station Re- nicator/Transmitter 20 AFM-16ATF Annunciator 22 porting 151, 152 data MS-9600 PN 51335:E 7/9/03...
  • Page 158 Monitor module 19 control module 69 service/program keys 16 adjective 66 detector 50 keyboard and keypad 43 enable/disable 62 detector screens 51 Keypad/Display noun 67 module, monitor 61 removal and installation 32 noun/adjective 65 EIA-232 39 type 63 MS-9600 PN 51335:E 7/9/03...
  • Page 159 130, 131 nonsilenceable power exiting 44 waterflow 94 NAC 12 history 129 nonsilenceable waterflow 79 nonresettable 14 NAC 128 normal display 44, 113 resettable 71 power 126 Notification Appliance Circuit 14, resettable smoke 14 Print 133 MS-9600 PN 51335:E 7/9/03...
  • Page 160 NAC Style Z 30 reference manual 14 Timers 81 SLC-2 38 resistance 14 Transmitter Module 36 wiring control modules see also Signaling Line Circuit see also 4XTMF module 20 see also Style Y or Style Z 19 MS-9600 PN 51335:E 7/9/03...
  • Page 161 Maintenance Level 109 zone type 79 list 79 Zone Z97 54 Zone Z98 pre-signal zone 54 Zones 125, 140 see also software zones 12 Zones Disabled 78 Zones Enabled 78 Zones Installed 78 zones per device 55 MS-9600 PN 51335:E 7/9/03...
  • Page 162 Notes MS-9600 PN 51335:E 7/9/03...
  • Page 163: Limited Warranty

    Limited Warranty The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service.
  • Page 164 World Headquarters One Fire-Lite Place, Northford, CT 06472-1653 USA 203-484-7161 • Fax 203-484-7118 www.firelite.com...

This manual is also suitable for:

Ms-9600e

Table of Contents

Save PDF