NFPA Standard-Specific Requirements
NFPA 72 Remote Station Protective Signaling System
Notes:
1.
Cut Jumper JP3 on the MS-9200UDLS main circuit board to supervise placement of the
4XTMF module.
2.
Refer to "4XTMF Transmitter Module Installation" on page 39 for detailed information.
Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.
Figure C.2 Remote Station Connection Using 4XTMF Module
172
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver Model RS82.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Polarity Shown is
Normal Standby
+
-
+
Power-limited
-
(Dummy load with a 4.7K
, ¼ watt resistor
when no connection is made)
4XTMF Transmitter Module