Programming
Monitor module type selection will affect the function of the point as follows:
Monitor Type
Pull-Station
User-Defined-1
Waterflow
User-Defined-2
Monitor
User-Defined-3
Future
Future
Smoke-Conventional
User-Defined-5
Heat-Conventional
User-Defined-6
Medic-Alert
User-Defined-7
Hazard-Alert
User-Defined-8
Tornado-Alert
User-Defined-9
Phone
User-Defined-10
Tamper
User-Defined-11
Supervisory
User-Defined-12
Supervisory-AR
User-Defined-13
HVAC OVRRIDE
Power-Monitor
User-Defined-14
Trouble-Monitor
User-Defined-15
Process-Monitor
User-Defined 16
Process-Monitor-AR
User-Defined-17
MNS Event
Future
Ack-Switch
Sil-Switch
Reset-Switch
Drill-Switch
PAS-Bypass
HVAC RESTART
Drill-Switch-AR
1 Combination systems employing these non-fire monitor types require the SLC
2 For entries ending in AR, AR refers to AutoResettable.
3 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to "Monitor
78
Action When Activated
Fire Alarm
same as previous (Pull-Station)
Fire Alarm Delayed
same as previous (Waterflow)
Fire Alarm
same as previous (Monitor)
not used
not used
Fire Alarm
same as previous (Smoke-Conventional)
Fire Alarm
same as previous (Heat-Detector)
1
General Purpose Signaling, latching
same as previous (Medic-Alert)
1
General Purpose Signaling, latching
same as previous (Hazard-Alert)
1
General Purpose Signaling, latching
same as previous (Tornado-Alert)
Active Phone (LCD display only)
same as previous (Phone)
Supervisory, nonlatching (tracking)
same as previous (Tamper)
Supervisory, latching
same as previous (Supervisory)
2
Supervisory, nonlatching (tracking)
same as previous (Supervisory-AR)
3
Switch Supervisory, nonlatching (tracking)
Power Fault
same as previous (Power Monitor)
Trouble
same as previous (Trouble Monitor)
General Purpose Signaling, latching
1
same as previous (Process-Monitor)
1,2
General Purpose Signaling, nonlatching (tracking)
same as previous (Process-Monitor-AR)
Allows the Mass Notification System to override FACP programming and
turn off designated active outputs
not used
Acts like panel Acknowledge Key
Acts like panel Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
3
Switch (see note 2)
2
Acts like panel Drill Key, nonlatching (tracking)
Table 3.1 Monitor Types
loop to be programmed by the installer for Style 4 operation and isolator modules
must be employed on each non-fire branch of the SLC as per Figure 13 in the
SLC Wiring Manual (document number 51309). Fire and non-fire devices must
not be used on the same SLC branch. For UL2017 compliance, The ANN-LED
annunciator must be used to indicate the active, dedicated zone or device
Module Operation" on page 180.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Master Programming Level