Master Programming Level
When Autoprogram is selected, the control panel will begin autoprogramming the system by
communicating with each addressable device installed on the SLC loop. While autoprogramming,
the panel will display the following:
When Autoprogramming is completed, the control panel will display the type and quantity of each
device installed on the SLC loop similar to the following display:
In the preceding example, the display indicates that the SLC Loop has 55 addressable detectors, 35
monitor modules and 30 control modules installed.
Pressing the ESC key will return the display to Programming Screen #1.
3.6.2 Point Program
PROGRAMMING
1=AUTOPROGRAM
The Point Program option allows the programmer to add a new addressable device to an SLC loop,

2=POINT PROGRAM

delete an existing device from a loop or change the programming for an existing device. Pressing
3=ZONE SETUP
Programming Screen #1
2, while viewing Programming Screen #1, will select the Point Program option and display the
following screen:

Detector Programming

Pressing 1, while viewing the Point Program Screen, will allow the programmer to add, delete or
change the programming of an addressable detector. The following screen will be displayed by the
control panel:
Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows the
programmer to add a new detector address to programming:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 005.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
AUTOPROGRAM
AUTOPROGRAMMING!
PLEASE WAIT
Autoprogram Progress Screen
# OF DET LOOP1 055
# OF MON LOOP1 035
# OF CON LOOP1 030
Autoprogram Result Screen #1
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
ADD DETECTOR
ENTER DETECTOR#

Add Detector Screen
Programming