Test Its-Dx4020-G Communications - Bosch ICP-EZM2 Easy Series System Reference Manual

Easy series
Hide thumbs Also See for ICP-EZM2 Easy Series:
Table of Contents

Advertisement

Easy Series
2.8.3

Test ITS-DX4020-G Communications

1.
2.
3.
4.
Bosch Security Systems, Inc.
Configure the control panel for cellular communication, if necessary. Refer to
Section 2.8.1 Configure the Control Panel for Cellular Communication, page 25.
Send a test alarm using the GPRS network route, and then verify receipt of the alarm at
the CMS.
For systems using a ITS-DX4020-G with Network as the Primary Format (GPRS) and
Contact ID or SIA as the Backup Format (GSM), program and use a Manual Communicator
Test using Programming Item Number 362 (refer to Section System Report and Restoral
Routing, page 51). Then, send a test report using the PTSN using GSM destination and
observe the LEDs. Refer to Section 2.8.3 Test ITS-DX4020-G Communications, page 27 for
configuration information. To use the Manual Communicator Test:
a) Set the Format for Route 2 Primary Destination (Programming Item Number 213) the
same as the Format for Route 1 Backup Destination (Programming Item Number 212)
b) Set the Route 2 Primary Destination (Programming Item Number 208) the same as the
Route 1 Backup Destination (Programming Item Number 207).
c) Set Programming Item Number 362 to 2 (Route 2 only).
d) Set Programming Item Number 202 to 1.
If incoming GSM calling is enabled, initiate a phone call into the control panel voice
menu.