Initial Setting Examples - Omron E5CZ User Manual

Digital temperature controller with 11-segment display
Hide thumbs Also See for E5CZ:
Table of Contents

Advertisement

Initial Setting Examples

3-1

Initial Setting Examples

Explanation of Examples
Example 1
Input type:
Control method: ON/OFF control
Alarm type:
Alarm value 1:
Set point:
32
Initial hardware setup, including the sensor input type, alarm types, control
periods, and other settings is done using parameter displays. The O and M
keys are used to switch between parameters, and the amount of time that you
press the keys determines which parameter you move to.
This section describes two typical examples.
Changing Parameters
in-t
0
in-h
100
M
M
in-l
0
M
cntl
cntl
onof
onof
Setup Procedure
5 (K thermocouple,
−200°C to 1,300°C)
Power ON
2 (upper limit)
20°C (deviation)
100°C
Initial Setting
Level
Set input
specifications
Set control
specifications
Set alarm type
Operation
Level
Set alarm values
Start operation
A
image means that there are parameters.
Continue pressing the M key to change parameters
until you reach the intended parameter.
Changing Numbers
C
25
Numeric data and selections in each
0
screen can be changed by using the
U and D keys.
Power ON
Operation
Level
C
25
Press the O key for
at least 3 s.
Initial Setting
Level
in-t
Check input type.
M
Check that
cntl
control method is
onof
ON/OFF control.
M
Check alarm type.
alt1
M
Press the O key for
at least 1 s.
Operation
Level
C
25
Use the U and
D keys to set the
100
SP to 100°C.
M
r-s
Confirm that
control is running.
run
M
Use the U and
C
al-1
D keys to set the
20
alarm value to
20°C.
M
Start operation.
Section 3-1
PV/SP
0
Control stops.
Input type: 5
5
ON/OFF
onof
control:
PID
pid
control:
Alarm 1 type: 2
2
Control starts.
PV/SP:
100
Running
run
Stopped:
stop
20
Alarm value 1: