Environmental Requirements - Sun Oracle SPARC T4-4 Installation Manual

Table of Contents

Advertisement

Environmental Requirements

Specification
Temperature
Relative
Humidity
Altitude
Vibration
Shock
* Except in China markets where regulations may limit installations to a maximum altitude of 2000 m.
Related Information
"Physical Specifications" on page 5
"Input Power Information" on page 7
8
SPARC T4-4 Server Installation Guide • May 2014
Operating
• Sea level to 2953 ft. (900m):
41°F to 95°F (5°C to 35°C)
• Above 2953 ft. (900m):
Decrease the maximum allowable
temperature by 1.6°F/1000 ft
(1°C/300m)
IEC 60068-2-1 Test Ad, and
60068-2-2 Test Bd
10 to 90% RH, 27°C maximum wet
bulb (noncondensing)
IEC 60068-2-56 Test Cb
*
10,000 ft. (3,000m)
IEC 60068-2-13 Test M, and
60068-2-41 Test Z/BM
0.15 G (z-axis),
0.10 G (x-, y-axes), 5-500Hz swept
sine
IEC 60068-2-6 Test Fc
3 Gs, 11 ms half-sine
IEC 60068-2-27 Test Ea
Nonoperating
-40°F to 149°F (-40°C to 65°C)
IEC 60068-2-1 Test Ab and 60068-2-2
Test Bb
93% RH, 35°C maximum wet bulb
(noncondensing)
IEC 60068-2-56 Test Cb
40,000 ft. (12,000m)
IEC 60068-2-13 Test M
0.5 G (z-axis),
0.25 G (x-, y-axes), 5-500Hz swept
sine
IEC 60068-2-6 Test Fc
• Roll-off:
1-inch roll-off free fall, front to back
rolling directions
• Threshold:
25 mm threshold height at 0.75 m/s
impact velocity