N700 Operating Instructions and Parts Manual
(4) When the operation command is turned on after the power supply input, the inverter drives
normal. (Example 3)
(5) Assign 13(USP) to an intelligent input terminal 1~8(I001~I008). Unattended start protection is
shown as follows:
(Example1)
power supply
FW
USP
RS
Alarm
output
(6) When an error is reset in state that input a driving order in the terminal after USP error occurs,
the inverter will restart automatically. Please take care. (Example 2)
9.2.11

Software lock mode selection (SFT : Software Lock)

(1) It is selectable whether the data in a code is changeable in this function.
(2) This function is used to prevent changing data by mistake.
(3) When you want to use an intelligent input terminal 1~8(I001~I008), assign 15(SFT).
Function
Code
name
Software
lock
I047
mode
selection
P24 PLC
(Example2)
power supply
Fig. 9- 18 In case of setting USP function to an input terminal 1(I001=13).
Initial
Setting
Unit
value
range
1
-
Table 9- 10 Software lock mode selection (SFT)
---
2
1
CM1
RESET
USP
(17)
(13)
FW
USP
RS
Alarm
output
0
All parameters except I047 are locked when SFT is on
1
All parameters except I047, F001 are locked when SFT is on
All parameters except I047, F001 and User group are locked
2
when SFT is on
3
All parameters except I047 are locked)
4
All parameters except I047, F001 are locked
5
All parameters except I047, F001 and User group are locked
96
9. Explanation of I-Group Function
FW
CM1
FWD
(0)
(Example3)
power supply
FW
USP
RS
Alarm