Monitor Output Signals (Am/Ami, Fm) - Hyundai n 700 Instruction Manual

Hide thumbs Also See for n 700:
Table of Contents

Advertisement

N700 Operating Instructions and Parts Manual
10.3

Monitor output signals (AM/AMI, FM)

10.3.1
Digital output signals (FM) selection (o009~o011)
(1) The FM control terminal can monitor the output frequency and output current.
(2) FM terminal is a PWM (Pulse Width Modulation) output.
Function
Code
name
FM output
o009
Selection
Note)
o009 =2 (output torque) is only outputted when control mode is SLV, SLV2, V2, 0Hz - V2
display.
(3) PWM signal type: o009 = 0, 1, 2, 4, 5, 6, 7
① PWM (Pulse-Width Modulation) signal is used to run a moving-coil type indicator. PWM
signal is expressed by analog value that is AUTO meaning value by moving-coil type
indicator.
② The maximum value of FM signal is 12V. The value is changeable by adjusting in FM
control(o011).
Note)
Initial
Unit
value
0
-
Table 10- 17 FM output Selection(o009)
Fig. 10- 12 The waveform of FM signal (o009 = 0, 1, 2, 4, 5, 6, 7)
Fig. 10- 13 Method that displaying FM signal by using an analog
Standard analog signal is displayed through AM and AMI terminal.
Please use the circuit like this picture to output analog signal by using PWM signal of
FM terminal.
Setting
Contents
range
0
Fo : Output frequency
1
Io : Output current
2
To : Output torque
Fo.D : Digital output
3
frequency
4
Vo : Output voltage
5
Pin : Input delctric power
Load : The rate of thermal
6
load
7
Flad : LAD frequency
120
10. Explanation of O-Group
Full Scale Value
0~ Maximum frequency (Hz)
0~200%
0~200%
0~ Maximum frequency (Hz)
0~100%
0~200%
0~100%
0~ Maximum frequency (Hz)

Hide quick links: