9.2.13

Reset (RESET)

(1) This function resets the inverter when a protective trip has occurred.
(2) The method of reset is to either push the STOP/RESET key on the digital operator or to
switch the Reset terminal ON.
(3) To reset the inverter with the control terminal, assign 17(RESET) to an intelligent input
terminal.
(4) Reset selection I051 selects when the alarm signal is cancelled and whether it is valid or
invalid in normal operation.
Code
Function name
I050
Reset selection
Reset frequency
I051
matching
selection
(5) Use the RESET terminal as the a-contact (Normally open). If the RESET terminal is set to b-
contact, the inverter is always RESET.
(
Example
RS
Alarm
9.2.14
Wire(3-Wire) input function(STA,STP, F/R)
(1) This function is used when a momentary push start/stop control is required.
(2) Set the operation command selection F011 to control terminal (1).
(3) Assign 18 (STA), 19 (STP) and 20 (F/R) to three of the intelligent input terminals, and the
operation becomes possible as follows. When the terminal is assigned STP terminal, FW
terminal and also RV terminal become invalid. If all three input are not assigned this function
will not operate.
Initial
Unit
value
0
-
0
-
Table 9- 13 Reset selection
1)
Fig. 9- 21 Example of the reset selection
9. Explanation of I-Group Function
Setting
range
At ON, trip cancellation : when is normal, validation
0
(output cutting) (ex 1)
At OFF, trip cancellation : when is normal, validation
1
(output cutting) (ex 2)
At ON, cancellation (when is normal) trip : when is
2
normal, nullity (trip cancellation)
0
0Hz : 0Hz start
1
Fmat : Frequency matching start (ex 3)
(
Example
RS
Alarm
99
Contents
2)