N700 Operating Instructions and Parts Manual
(4) Set output current level at overload in overload advance notice level 1 (o026).
Code
Function name
Overload advance
o026
notice level 1
Overload advance
o027
notice level 2
10.2.4

The Maximum PID Deviation Level (OD)

(1) It is possible to establish the maximum deviation level o029 on PID control. When the PID
deviation amount reaches the set level o029, it is possible to output OD(PID Max deviation) in
an intelligent output.
(2) o029 can be set from 0 to 100.0 % and corresponds with the command : from 0 to maximum
value.
Code
Function name
o029
(3) Assign 04 (OD) to intelligent output terminal 1~4 (o001~o004)
Code
Function name
value
4
OD PID deviation
Initial
value
1.0
1.0
Table 10- 9 Overload advance notice level setting
Fig. 10- 11 Overload advance notice level setting
Initial
value
PID deviation
3.0
setting level
Table 10- 10 PID deviation setting level(o029)
Output
status
OFF
ON
Table 10- 11 OD PID deviation code value
Setting
Unit
range
Inverter rated current ⅹ 0. ~ 2.0 times
times
0.0~2.0
When reach overload advance notice
level 1 OL signal output
Inverter rated current ⅹ 0. ~ 2.0 times
times
0.0~2.0
When reach to overload advance notice
level 1 OL signal output
Setting
Unit
range
Setting deviation range between the set
%
0.0~100.0
In case PID error is less than the setting value of deviation
signal
In case PID error is more than the setting value of deviation
signal
116
10. Explanation of O-Group
Contents
Contents
value and feedback value.