Analog Output Signals (Am/Ami) Selection (O012~O017) - Hyundai n 700 Instruction Manual

Hide thumbs Also See for n 700:
Table of Contents

Advertisement

N700 Operating Instructions and Parts Manual
10.3.2

Analog output signals (AM/AMI) selection (o012~o017)

The AM terminal and the AM1 terminal can monitor
the output frequency or the output current.
The AM terminal has an analog output of 0-10V.
The AMI terminal has an analog output of 4-20mA.
(1) AM/AMI output signals selection
Select a signal to output from the following options.
Function
Code
name
AM
o012
Output
Selection
AMI
o015
Output
Selection
Note) Display o012/o015=2(output torque) only at the time of SLV, SLV2, and V2
(2) AM/AMI adjustment
This function is used to calibrate a meter connected to the AM and AM1 terminal.
Code
o013
AM offset
o014
AM adjustment
o016
AMI offset
o017
AMI adjustment
Initial
Setting
Unit
value
range
0
1
2
0
-
3
4
5
6
0
1
2
0
-
3
4
5
6
Table 10- 19 AM/AMI output signals selection
Function name
Initial value
Table 10- 20 AM/AMI adjustment
Explanation
Fo : Output frequency
Io : Output current
To : Output torque
Vo : Output voltage
Pin : Input electric power
Load : Thermal load ratio
Flad : LAD frequency
Fo : Output frequency
Io : Output current
To : Output torque
Vo : Output voltage
Pin : Input electric power
Load : Thermal load ratio
Flad : LAD frequency
Unit
Setting range
0.96
-
100.0
-
4.00
-
100.0
-
122
10. Explanation of O-Group
AM
AMI
L
GND
4~20mA analog current output
0~10V analog voltage output
Full Scale Value
0~ Maximum frequency (Hz)
0~200%
0~200%
0~100%
0~200%
0~100%
0~ Maximum frequency (Hz)
0~ Maximum frequency (Hz)
0~200%
0~200%
0~100%
0~200%
0~100%
0~ Maximum frequency (Hz)
Contents
0.00~10.00
Offset setting
0.0~255.0
Gain setting.
0.00~20.00
Offset setting
0.0~255.0
Gain setting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hi run n 700

Table of Contents