⑥ When a relay is used as an intelligent output, connect a diode for surge protection parallel
to the relay coil.
⑦ Do not short the analog voltage terminals H and L or the internal power terminals PV24
and all CM1's. Otherwise there is risk of Inverter damage.
⑧ When connecting a thermistor to the TH and all CM1's terminal, twist the thermistor
cables and separate them from the rest. Limit the connection wires to 65 feet.
(3) Change of input logic type
The logic type of intelligent input terminals is on the following list (Factory Default).
N700 Inverter(5.5㎾ ~ 132㎾)
The input logic type can be changed by changing the Short bar connection of control terminal.
(4) The connection to the input programmable logic controller (sequencer)
To use interface power within inverter
Sink type
Source type
Sink TYPE
Between P24 and PLC on the control terminal.
Between PLC and CM1 on the control terminal.
To use outside power
(Remove the short bar off of the control
18
2. Installation and Wiring