Entry Delay (0310 - 0360); Exit Delay (0311 - 0361); Extended Delay (0312 - 0362) - GE Concord 4 Series Installation Instructions Manual

Security systems
Hide thumbs Also See for Concord 4 Series:
Table of Contents

Advertisement

Entry Delay (0310 - 0360)

This setting determines how much time the user has to disarm the system
(after entering the armed premises through a "designated delay door")
without causing an alarm.
Note
For UL 1023 Listed installations, the Entry Delay must be set to 45 seconds or
less. The combined time for the Entry Delay and Dialer Abort Delay (02006)
must not exceed 60 seconds.

Exit Delay (0311 - 0361)

This setting determines how much time the user has (after arming the sys-
tem) to leave the premises through a "designated delay door" without
causing an alarm.
Note
For UL 1023 listed installations, this feature must be set to 60 seconds or less.
For UL 1610 listed installations, this feature must be set to 120 seconds or less.

Extended Delay (0312 - 0362)

This setting determines how much time the user has (after arming the sys-
tem) to enter or exit the premises through a "designated extended delay
door" (1–8 minutes).
Note
For UL Listed installations Extended Delay may not be used.
Siren Timeout (0313 - 0363)
This setting determines how long sirens sound (1–30 minutes) if
no one is present to disarm the system.
Note
For UL Listed installations, the Siren Timeout must be set to 4 min-
utes or more.
Sleep Time (0314 - 0364)
This setting determines the start time and restart of a 10-hour window
during which trouble beeps are suppressed. The initial occurrence of
an event that causes trouble beeps within this window will not sound
trouble beeps until the Sleep Time window expires. If trouble beeps
from a previous event are due to be restarted during the sleep time
window, they will be restarted one hour prior to Sleep Time.
Note
For UL listed installations, this feature must be set to off.
41
The following sections describe the settings that appear under
WWW.DIYALARMFORUM.COM
Timers-Partition 1-6 (Default = 30 sec.)
To set the Entry Delay:
1.
With the display showing
(current setting), enter the desired time
SECS
value (30–240). The display flashes the
entered setting.
2.
Press # and the display shows the new setting.
Timers-Partition 1-6 (Default = 60 sec.)
To set the Exit Delay:
1.
With the display showing
(current setting), enter the desired time
SECS
value (45–184). The display flashes the
entered setting.
2.
Press # and the display shows the new setting.
Timers-Partition 1-6 (Default = 4 min.)
To set the Extended Delay:
1.
With the display showing
(current setting), enter the desired
MINUTES
time value (1–8). The display flashes the
entered setting.
2.
Press # and the display shows the new setting.
Timers-Partition 1-6 (Default = 4 min.)
To set the Siren Timeout:
1.
With the display showing
(current setting), enter the desired time value (1–30).
The display flashes the entered setting.
2.
Press # and the display show the new setting.
Timers-Partition 1-6 (Default = 22:00 [10:00 pm])
To set the Sleep Time:
1.
With the display showing
rent setting), enter the desired time value (00:00-
23:50 using 10 minute intervals). The display
flashes the entered setting.
2.
Press # and the display show the new setting.
To turn off Sleep Time:
1.
With the display showing
rent setting), press D.
.
PARTITION 1-6
ENTRY DELAY nnn
EXIT DELAY nnn
EXTENDED DELAY n
SIREN TIMEOUT nn MINUTES
SLEEP TIME hh:mm
SLEEP TIME hh:mm
Concord 4 Series Systems