Horizontal Vent Heat Shield Installation; Framing; Wall Enclosure Rough Opening; Minimum Finished Opening Dimensions - kozy heat MINNETONKA 55345-MV Installation Manual

Direct vent gas fireplace
Table of Contents

Advertisement

HORIZONTAL VENT HEAT SHIELD INSTALLATION

The horizontal vent heat shield must be installed when using a 45-degree elbow to horizontally position the vent system.
IMPORTANT
EXCEPTION: Corner installations
1.
Loosen, but do not remove center three screws at back of fireplace as shown.
2.
Bend horizontal vent heat shield at perforation to a 45° angle. Slide (3) slots on
horizontal vent heat shield under loosened screws. Re-tighten screws.

WALL ENCLOSURE ROUGH OPENING

Framing dimensions should allow for wall covering thickness and fireplace facing materials. If using a hearth, ad just rough
opening size as necessary to maintain at least minimum clearance requirements.
IMPORTANT
Non-combustible facing material may be applied over (but not directly to) fireplace face. This will prevent facing material from
falling off due to heat expansion. Do not obstruct the flow of ventilation air.

MINIMUM FINISHED OPENING DIMENSIONS

HORIZONTAL VENTING: 44-1/2"(1130mm) High x 41-3/8"(1051mm) Wide x 21-7/8" (556mm) Deep.
VERTICAL VENTING: 44-1/2"(1130mm) High x 41-3/8"(1051mm) Wide x 23-7/8" (606mm) Deep.
Maintain all clearances as stated in this manual.
Provide adequate clearance in front of fireplace to operate lower grill, open and close optional decorative doors / full door faces,
NOTE
access components, installation of gas line, fan, etc.
Do not obstruct upper and lower grill openings. Room air enters through lower passage, is heated and exits through upper
WARNING
passage. Blocking these passages may result is overheating, creating a potentially hazardous situation.
*
Illustration requires a minimum 5" (127mm) exterior wall depth when using
minimum horizontal venting. Anything less than a 5" (127mm) exterior wall
depth requires that you add that depth to the 21-7/8" (556mm) dimension to
accommodate minimum venting.
5" (127 mm) exterior wall depth shown*
Figure 8b
PREPARE THE FIREPLACE

FRAMING

Figure 8a
12-1/2" x (318mm) H x 10-7/8" (277mm) W opening
(required for horizontal terminations)
44-1/2"
(1130mm)
41-3/8"
(1051mm
8
Attach here.
Tighten screws.
21-7/8"
Hearth
(556mm)
Height