Horizontal Terminations - kozy heat MINNETONKA 55345-MV Installation Manual

Direct vent gas fireplace
Table of Contents

Advertisement

HORIZONTAL TERMINATIONS

HORIZONTAL VENT SYSTEM CLEARANCES
ALL APPROVED VENTING
NOTE
Horizontal sections require 1/4" (6mm) rise for every 12" (305mm) of travel.
MINIMUM: 45° elbow + 6" (152mm) horizontal + termination cap.
MAXIMUM: U.S. Installations: 45° elbow + 10ft. (3.05m) + termination cap.
Canadian Installations: 0-2000ft. (0-607m): 45˚ elbow + 10ft. (3.05m) + termination cap.
2000-4500ft. ( 607-1372m): 45˚ elbow + 10ft. (3.05m) + termination cap. Must de-rate burner orifices: Nat. Gas: #56 & #35
The horizontal vent heat shield must be installed when using a 45-degree elbow to horizontally position the vent system.
Exception: corner installations
IMPORTANT
Kozy Heat Wall Pass-thru, #800-WPT (4-1/2" (114mm) - 6-1/2" (165mm) wall thickness) or #800-WPT2 (6-1/2" (165mm) - 12-
1/2" (318mm) wall thickness), must be used on all horizontal vent runs.
TYPICAL HORIZONTAL INSTALLATION
Figure 14a
VENTING
TOP
3 inches (76mm)
Termination Cap
Horizontal Vent Heat Shield
45° Elbow
Minimum: 6" (152mm)
Maximum: 10ft. (3.05m)
BOTTOM
1 inch (25mm)
TYPICAL CORNER INSTALLATION
Termination Cap
Pipe
90° Elbow
45° Elbow
Vent Opening Dimensions for corner installations:
Refer to vent pipe manufacturer's instructions.
Figure 14b
14
SIDES
1 inch (25mm)
L.P. Gas: #69 & #52