Horizontal Vent Heat Shield Installation Instructions; Horizontal Termination Minimum / Maximum; Horizontal Min. / Max. Venting Illustrations - kozy heat Alpha ALP-36-L Installation And Operation Manual

Direct vent gas fireplase
Hide thumbs Also See for Alpha ALP-36-L:
Table of Contents

Advertisement

HORIZONTAL VENT HEAT SHIELD
1.
Loosen, but do not remove center two screws on top of fireplace.
2.
Bend horizontal heat shield at perforation to a 90° angle. Slide (2) slots on horizontal vent heat shield under loosened screws.
3.
Re-tighten screws.
ATTACHMENT SCREWS
Figure 20a
HORIZONTAL TERMINATIONS
MINIMUM: 18" (457mm) minimum vertical rise + 90° elbow + 9" (229mm) minimum horizontal + termination cap.
MAXIMUM: 18" (457mm) minimum vertical rise + 90° elbow + 20ft. (6.1m) maximum horizontal + termination cap.
TERMINATION CAP
HORIZONTAL VENT
HEAT SHIELD
90° ELBOW
HORIZONTAL RUN
VERTICAL RISE
Figure 20b
VENTING
MINIMUM:
18" (457mm) minimum vertical rise / 9" (229mm) minimum horizontal
MAXIMUM:
18" (457mm) minimum vertical rise / 20ft. (6.1m) maximum horizontal