Horizontal Min. / Max. Venting Illustrations; Horizontal Vent Heat Shield Installation Instructions - kozy heat Delano DEL-36 Installation And Operation Manual

Direct vent linear fireplace
Table of Contents

Advertisement

NOTE: Page 19 has information on restrictor installation in conjunction with venting installation. Page 40 has information on restrictor
recommendations depending on burner flame appearance and instructions on installation after venting is completed.
MIN. / MAX. HORIZONTAL VENTING
HORIZONTAL VENT
HEAT SHIELD
Figure 17a
IMPORTANT: The horizontal vent heat shield must be installed when using a 90-degree elbow to horizontally position the vent system.
Kozy Heat Wall Pass-thru, #800-WPT (4-1/2" (114mm) - 6-1/2" (165mm) wall thickness), or
#800-WPT2 (6-1/2" (165mm)-12-1/2" (318mm) wall thickness) must be used on all horizontal vent runs.
HORIZONTAL VENT HEAT SHIELD
IMPORTANT: The horizontal vent heat shield must be installed when using a 90-degree elbow to horizontally position the vent system.
This includes any corner installation.
CAUTION: This gas appliance must not be connected to or joined with any other chimney flue serving another appliance.
1.
Loosen, but do not remove center three screws on top of fireplace.
2.
Bend horizontal heat shield at perforation to a 90° angle. Slide (3) slots on horizontal vent heat shield under loosened screws.
3.
Re-tighten screws.
ATTACHMENT SCREWS
Figure 17b
VENTING
MINIMUM: 6in. (152mm)
MAXIMUM: 25ft. (7.62m); 30ft. (9.14m) when using stainless
steel pipe for entire length of termination.
90° ELBOW
TERMINATION CAP
PAGE 17