ACS 400 Complete Parameter List

Initially, only the so called basic parameters (shaded grey in Table 12) are visible. Use the
appropriate menu function of the control panel to make the full parameter set visible.
S = Parameters can be modified only when the drive is stopped.
M = Default value depends on the selected macro (*).
Table 12 Full parameter set.
Code Name
Group 99
START-UP DATA
9901
LANGUAGE
9902
APPLIC MACRO
9905
MOTOR NOM VOLT
9906
MOTOR NOM CURR
9907
MOTOR NOM FREQ
9908
MOTOR NOM SPEED
9909
MOTOR NOM POWER
9910
MOTOR COS PHI
Group 01
OPERATING DATA
0102
SPEED
0103
OUTPUT FREQ
0104
CURRENT
0105
TORQUE
0106
POWER
0107
DC BUS VOLTAGE
0109
OUTPUT VOLTAGE
0110
400
ACS
TEMP
0111
1
EXTERNAL REF
0112
2
EXTERNAL REF
0113
CTRL LOCATION
0114
(
)
RUN TIME
R
0115
kWh
(
COUNTER
0116
APPL BLK OUTPUT
0117
1-
4
DI
DI
STATUS
0118
1
AI
0119
2
AI
0121
5 &
DI
RELAYS
0122
AO
0124
1
ACTUAL VALUE
0125
2
ACTUAL VALUE
0126
CONTROL DEV
ACS 400 User's Manual
Range
0 - 12
0 - 8
200, 208, 220, 230, 240,
380, 400, 415, 440, 460,
480 V
0.5*I
- 1.5*I
N
0 - 250 Hz
0 - 3600 rpm
0.1 - 100 kW
0.50 - 0.99
0 - 9999 rpm
0 - 250 Hz
-
-
-
0 - 999.9 V
0 - 480 V
0 - 150 °C
0 - 250 Hz
0 - 100 %
0 - 2
0 - 9999 h
)
0 - 9999 kWh
R
0 - 100 %
0000 - 1111
(0 - 15 decimal)
0 - 100 %
0 - 100 %
0000 - 0111
(0 - 7 decimal)
0 - 20 mA
0 - 100 %
0 - 100 %
-100 - 100 %
Resolution Default
1
1
-
0.1 A
N
1 Hz
1 rpm
0.1 kW
0.01
1 rpm
0.1 Hz
0.1 A
0.1 %
0.1 kW
0.1 V
0.1 V
0.1 °C
0.1 Hz
0.1 %
1
1 h
1 kWh
0.1 %
1
0.1 %
0.1 %
1
0.1 mA
0.1 %
0.1 %
0.1 %
User
0 (
)
ENGLISH
0 (
)
FACTORY
230 V / 400 V
1.0*I
N
50 Hz
1440 rpm
2 - 30 kW
0.83
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
S
M
á
á
á
á
á
á
á
55

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents