Register Mapping

The drive parameters are mapped to the 4xxxx area so that:
40001 – 40099 are reserved for drive control registers
40101 – 40199 is reserved for the actual values (parameter group 1)
40201 – 40299 is reserved for parameter group 2
40301 – 40399 is reserved for fault and alarm information
... other parameter groups
49901 – 49999 is reserved for the start-up data
Register addresses 4GGPP are shown in Table 24. In this table GG is the group number, and PP is
the parameter number within the group.
Table 24 Parameter mapping.
4GGPP
40001 – 40006
00 Drive control registers
40102 – 40130
01 OPERATING DATA
41001 – 41003
10 COMMAND INPUTS
41101 – 41108
11 REFERENCE SELECT
...
...
49901 – 49908
99 START-UP DATA
The register addresses between the groups are invalid. No reads or writes are allowed for these
addresses. If there is an attempt to read or write outside the parameter addresses, the Modbus
interface will return an exception code to the controller.
ACS 400 User's Manual
GG
01 Control word
02 Reference 1
03 Reference 2
04 Status word
05 Actual value 1
06 Actual value 2
02
SPEED
...
30
OLDEST FAULT
01
EXT
02
EXT
03
DIRECTION
01
KEYPAD REF SEL
...
08
CONST SPEED
...
02
APPLIC MACRO
...
08
MOTOR NOM SPEED
PP
1
COMMANDS
2
COMMANDS
7