Group 01: Operating Data

This group contains drive operating data, including actual signals and fault memories. Actual Signal
values are measured or calculated by the drive and they cannot be set by the user. Fault memories
can be cleared by the user from the control panel.
Code Description
0102 SPEED
Displays the calculated speed of the motor (rpm).
0103 OUTPUT FREQ
Displays the frequency (Hz) applied to the motor. (Also shown in OUTPUT display.)
0104 CURRENT
Displays the motor current, as measured by the ACS 400.
(Also shown in OUTPUT display.)
0105 TORQUE
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque.
0106 POWER
Displays the measured motor power in kW.
Note! ACS100-PAN will not display the unit ("kW").
0107 DC BUS VOLTAGE
Displays the DC bus voltage, as measured by the ACS 400. The voltage is displayed in Volts DC.
0109 OUTPUT VOLTAGE
Displays the voltage applied to the motor.
0110
ACS 400 TEMP
Displays the temperature of the ACS 400 heatsink in Centigrade.
0111
EXTERNAL REF 1
The value of external reference 1 in Hz.
0112
EXTERNAL REF 2
The value of external reference 2 in %.
0113
CTRL LOCATION
Displays the active control location. Alternatives are:
0 =
LOCAL
1 =
1
EXT
2 =
2
EXT
See "Appendix A", starting page 141 , for description of different control locations.
0114
RUN TIME (R)
Shows the total running time of the ACS 400 in hours (h). Can be reset by pressing UP and DOWN buttons
simultaneously when in parameter set mode.
0115
kWh COUNTER (R)
Shows the counted the kilowatt hours of ACS 400 in operation. Can be reset by pressing UP and DOWN
buttons simultaneously when in parameter set mode.
0116
APPL BLK OUTPUT
The reference value in per cent received from the application block. The value is from PID control or PFC
control, depending on the selected macro. Otherwise the value is from 0112
0117
DI1-DI4 STATUS
Status of the four digital inputs. Status is displayed as a binary number. If the input is activated, the display
will indicate 1. If the input is deactivated, the display will be 0.
ACS100-PAN
64
DI 4
DI 3
DI 2 DI 1
EXT REF
ACS-PAN
000001101BIN
2.