Code Description
8120 INTERLOCKS
Controls the use of the Interlock function.
Warning! If the Autochange function is used, also the Interlocks must be taken into use (see parameter
8118
AUTOCHNG INTERV
0 =
NOT SEL
No Interlocks function is in use. All digital inputs are available for other purposes.
1 = DI1
Interlocks function is in use. Depending on the number of motors, the digital inputs are reserved for the
interlock signals according to following table.
No of aux. motors
(param. 8117)
0
1
2
3
2 = DI2
Interlocks function is in use. Depending on the number of motors, the digital inputs are reserved for the
interlock signals according to following table.
No of aux. motors
(param. 8117)
0
1
2
3
ACS 400 User's Manual
).
Interlock signals
ACS 400 digital
inputs
DI1: Motor 1
DI2-DI5 free
DI1: Motor 1
DI2: Motor 2
DI3-DI5 free
DI1: Motor 1
DI2: Motor 2
DI3: Motor 3
DI4-DI5 free
DI1: Motor 1
DI2: Motor 2
DI3: Motor 3
DI4: Motor 4
DI5 free
ACS 400 digital
inputs
DI1: free
DI2: Motor 1
DI3-DI5 free
DI1: free
DI2: Motor 1
DI3: Motor 2
DI4-DI5 free
DI1: free
DI2: Motor 1
DI3: Motor 2
DI4: Motor 3
DI5: free
DI1: free
DI2: Motor 1
DI3: Motor 2
DI4: Motor 3
DI5: Motor 4
NDIO module 1
Not used
Interlock signals
NDIO module 1
Not used
NDIO module 2
Not used
NDIO module 2
Not used
109