Code Description
3 = DI3
Interlocks function is in use. Depending on the number of motors, the digital inputs are reserved for the
interlock signals according to following table.
No of aux. motors
(param. 8117)
0
1
2
3
4 = DI4
Interlocks function is in use. Depending on the number of motors, the digital inputs are reserved for the
interlock signals according to following table.
No of aux. motors
(param. 8117)
0
1
2
3
110
ACS 400 digital
inputs
DI1-DI2: free
DI3: Motor 1
DI4-DI5 free
DI1-DI2: free
DI3: Motor 1
DI4: Motor 2
DI5: free
DI1-DI2: free
DI3: Motor 1
DI4: Motor 2
DI5: Motor 3
DI1-DI2: free
DI3: Motor 1
DI4: Motor 2
DI5: Motor 3
ACS 400 digital
inputs
DI1-DI3: free
DI4: Motor 1
DI5 free
DI1-DI3: free
DI4: Motor 1
DI5: Motor 2
DI1-DI3: free
DI4: Motor 1
DI5: Motor 2
DI1-DI3: free
DI4: Motor 1
DI5: Motor 2
Interlock signals
NDIO module 1
Not used
DI1: Motor 4
DI2: Unused
Interlock signals
NDIO module 1
Not used
DI1: Motor 3
DI2: unused
DI1: Motor 3
DI2: Motor 4
NDIO module 2
Not used
Not used
NDIO module 2
Not used
Not used
ACS 400 User's Manual