ABB ACS 400 User Manual page 148

Frequency converter from 2.2 to 37 kw
Hide thumbs Also See for ACS 400:
Table of Contents

Advertisement

Table 35 Faults.
Fault Code
1
OVERCURRENT
2
DC OVERVOLTAGE
3
400
ACS
4 **
SHORT CIRCUIT
5
OUTPUT OVERLOAD
6
DC UNDERVOLTAGE
7
ANALOGUE INPUT
8
ANALOGUE INPUT
9
MOTOR OVERTEMP
10
PANEL LOSS
11
PARAMETERING
12
MOTOR STALL
13
SERIAL COMM LOSS
14
EXTERNAL FAULT SIGNAL
15 **
OUTPUT EARTH FAULT
138
Display
Description
Output current is excessive.
Intermediate circuit DC voltage is excessive.
ACS 400 heat sink temperature is excessive. Temperature trip limit is
OVERTEMP
95 °C.
Fault current. Possible reasons for this fault are:
Inverter overload condition. The ACS 400 output current exceeds the
ratings given on page 25 of this manual.
Intermediate circuit DC voltage is not sufficient.
1
Analogue input 1 loss. Analogue input value is less than
(1301). See also parameter 3001
2
Analogue input 2 loss. Analogue input value is less than
(1306). See also parameter 3001
Motor overtemperature condition as estimated by the ACS 400. Refer
to parameters 3004 – 3008.
Panel communication loss. Control panel is disconnected when the
drive is receiving start, stop and direction commands from the panel.
- Drive is in local control mode (LOC is shown in the control panel
display), or
- Drive is in remote control mode (REM is shown) and is parameterised
to accept start/stop, direction or reference from the panel. Refer to
parameters in groups 10 COMMAND INPUTS and 11 REFERENCE
SELECT.
See also parameter 3002
Parameter values are inconsistent:
Motor stall. This may be caused by excessive load or insufficient motor
power. Refer to parameters 3009 – 3012.
Serial communication through Standard Modbus Channel is lost.
External fault is active. See parameter 3003
Earth fault. The load on the incoming mains system is out of balance.
Motor load may be too high
Acceleration time may be too short (parameters 2202
1 and 2204
TIME
ACCELER TIME
Motor or motor cable is faulty or connected wrong.
Check mains for static or transient overvoltages
Deceleration time may be too short (parameters 2203
1 and 2205
TIME
DECELER TIME
Brake chopper (if present) may be underdimensioned
Check air flow and fan operation.
Check motor power against unit power.
There is a short-circuit in the motor cable(s) or motor
Supply disturbances
Mains phase may be missing
Fuse may be blown
PANEL LOSS
1 >
MINIMUM AI
MAXIMUM AI
2 >
MINIMUM AI
MAXIMUM AI
>
MINIMUM FREQ
MAXIMUM FREQ
PFC block tries to use IO extension module (NDIO) but the DDCS
link is not parameterised properly
Check connections between external control system and the
ACS 400.
Refer to parameters 5003
.
FUNC
There may be a fault in the motor or motor cable.
Motor cable may be too long.
2).
2)
<
.
AI
MIN FUNCTION
<
.
AI
MIN FUNCTION
.
1 (parameters 1301, 1302)
2 (parameters 1304, 1305)
(parameters 2007, 2008)
and 5004
COMM FAULT TIME
EXTERNAL FAULT
ACS 400 User's Manual
ACCELER
DECELER
1
MINIMUM AI
2
MINIMUM AI
COMM FAULT
.

Hide quick links:

Advertisement