ABB ACS800-67 System Description And Start-Up Manual

ABB ACS800-67 System Description And Start-Up Manual

Wind turbine converters
Hide thumbs Also See for ACS800-67:
Table of Contents

Advertisement

ABB wind turbine converters
System description and start-up guide
ACS800-67 wind turbine converters

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS800-67

  • Page 1 ABB wind turbine converters System description and start-up guide ACS800-67 wind turbine converters...
  • Page 2: List Of Related Manuals

    List of related manuals ACS800-67 manuals Code (English) ACS800-67 wind turbine converters for asynchronous slip ring 3AFE68392454 generators hardware manual ACS800-67 wind turbine converters system description and 3AUA0000095094 start-up guide Firmware manuals ACS800 IGBT supply control program firmware manual 3AFE68315735...
  • Page 3 System description and start-up guide ACS800-67 wind turbine converters Table of contents 3. Start-up with low voltage stator 4. Start-up with medium voltage stator  2017 ABB Oy. All Rights Reserved. 3AUA0000095094 Rev B EFFECTIVE: 2017-12-31...
  • Page 5: Table Of Contents

    ACS800-67 ........
  • Page 6 Encoder phasing ........... . 40 Stator phasing .
  • Page 7 ABB Drives communication profile ........
  • Page 8 Providing feedback on ABB manuals ........
  • Page 9: About This Manual

    ABB. Applicability This manual describes the standard ACS800-67 wind turbine converter but it can be applied to customized units as well. The control programs referred to in this manual are •...
  • Page 10: Target Audience

    10 About this manual Target audience This manual is intended for people who conduct start-ups and operate with the converter. Read the manual before working on the converter. You are expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols.
  • Page 11: Contents Of Other Related Manuals

    The manuals delivered with the converter are listed on the inside of the front cover of this manual. The table below lists the main subjects in each manual. When delivered Manual / Contents In all deliveries ACS800-67 wind turbine converters system description and start-up guide [3AUA0000095094 (English)] See section Contents of this manual on page 10.
  • Page 12: Further Information

    Address any inquiries about the product to your local ABB representative, quoting the type code and serial number of the unit. If the local ABB representative can not be contacted, address inquiries to nearest country that has support for wind turbine converters. See detailed contact information from the back cover of this manual.
  • Page 13: System Description

    System description 13 System description What this chapter contains This chapter describes the main components of a wind turbine and describes the functionality of the wind turbine converter as a part of a complete wind turbine system. General Variable-speed wind turbine concepts can be divided in two main categories, wind turbine systems equipped with a doubly-fed asynchronous generator or wind turbine systems equipped with an induction generator like squirrel-cage-, synchronous- or permanent magnet synchronous generator.
  • Page 14: Acs800-67

    Yaw motors ACS800-67  ACS800-67 is air-cooled four-quadrant wind turbine converter for wind turbine applications. The converter can be located up in the nacelle or in down tower of the wind turbine. The converter allows independent control of real and reactive flow in either direction (grid to rotor), or confined to unidirectional (rotor to grid) real power flow.
  • Page 15: Wind Turbine System With Low Voltage Stator (690 V)

    Wind turbine system with low voltage stator (690 V) MCB3 MCB1 ABRU MCB2 ACBU CONVERTER CTRL WIND TURBINE CTRL 1) Optional in ACS800-67 Wind turbine system with medium voltage stator (> 1000 V) MCB3 ABRU MCB2 ACBU CONVERTER CTRL WIND TURBINE CTRL No.
  • Page 16: Converter System

    16 System description Converter system  Doubly-fed asynchronous generators are essentially wound rotor induction machines with variable frequency excitation of the rotor circuit, incorporating rotor via frequency converter. Ability to convert mechanical energy into electrical energy (or vice versa) is based on electromagnetic induction.
  • Page 17 System description 17 U I cos 1 - cos grid stator grid stator P = T · Optional wind MCB3 MCB1 ABRU MCB2 ACBU CONVERTER CTRL Wind turbine controller U denotes phase-to-phase voltage, I phase current Below is a power versus speed curve example of a doubly-fed induction generator that has a synchronous speed of 1000 rpm and nominal speed of 1150 rpm.
  • Page 18: Control Of Generator Power

    18 System description Control of generator power The generator power can be controlled by adjusting torque or speed: · n P = T · = T · where generator power (W) generator torque (N·m) angular speed of the generator (rad/s) rotor mechanical speed (1/min rpm).
  • Page 19: Operational Speed Range Of A Typical Wind Turbine

    System description 19 Operational speed range of a typical wind turbine Wind power increases cubically as wind speed increases: · · A · v where wind power air density performance coefficient, tip speed ratio, pitch angle rotor surface wind speed. There is a minimum wind speed at which power generation is reasonable (cut-in speed) and a maximum speed at which the turbine can be operated safely (cut-out speed).
  • Page 20: Wind Turbine System Operating Speed Area

    20 System description Wind turbine system operating speed area The example below illustrates the generator speed control in different wind speed ranges. sync 2200 2200 2000 2000 1800 1800 1600 1600 1400 1400 1200 1200 1000 1000 cont.max Converter Converter operation is not operation is not allowed...
  • Page 21: Control Of Torque And Reactive Power Via Rotor-Side Converter

    System description 21 Control of torque and reactive power via rotor-side converter With DTC technology field orientation is achieved by using advanced generator theory to calculate the accurate generator torque. The performance of DTC controlled wind turbine converter is most effective and benefits are eg, fast torque response, accurate control also at low frequencies, torque repeatability and accuracy of dynamic and static speed operations.
  • Page 22 22 System description The basic DTC block selects the inverter switch states so that tangential motion of the flux vector is controlled by the torque error and the radial motion of the flux is controlled by the flux error. The torque reference is supplied by the WTC. The torque feedback is calculated by using stator-side quantities (at grid frequencies) ie, by a cross product of stator flux and stator current.
  • Page 23 System description 23 The rotor-side flux reference is chosen to achieve the desired power factor at the stator terminals. The operating flux level of the stator flux is completely dependent on the grid voltage and therefore the rotor flux reference is dependent on actual stator flux. The figure below shows the vector diagram of stator voltage, current and flux and rotor flux at leading and lagging power factors when the stator is regenerating to the electrical power network.
  • Page 24 24 System description An example curve of maximum reactive power capability as a function of the active power (power factor about 0.95 capacitive and 0.86 inductive) is shown below. Reactive power capability depends on the characteristics of the generator. Q (p.u.) Capacitive 0.75 Converter nominal power...
  • Page 25: Control Of Torque And Reactive Power Via Grid-Side Converter

    System description 25 Control of torque and reactive power via grid-side converter The fundamental theory of grid-side converter can be simplified to be analog to the synchronous generator. One voltage source is the electrical power network and the other voltage source is the grid-side converter. The voltages and currents can be presented as vectors.
  • Page 26 26 System description Reactive power is transferred only if there is an amplitude difference between the two voltage vectors. Reactive power transfer equation is following: For the desirable magnitude and direction of the power and reactive power flow, the length of the converter voltage vector and its phase angle (with respect to the grid voltage vector) must be controlled.
  • Page 27: Overview Of Converter Interfaces

    Overview of converter interfaces The WTC controls the converter using its main control word. For more information, refer to section ABB Drives communication profile on page 90. The start-up procedure of the converter is recommended to be proceeded with the DriveWindow PC tool.
  • Page 28: Converter Control

    28 System description Converter control General  The WTC operates as the overriding controller of the converter. It is connected to the NDCU control unit of the rotor-side converter via fieldbus. The rotor-side converter control program controls the rotor-side power modules according to the references and commands sent by the overriding controller.
  • Page 29: Fieldbus Control

    Fieldbus control of the grid-side converter is performed via the rotor-side converter NDCU control unit. The principle of reference and actual value chains in the control are shown in the diagram below. For details, see ACS800-67(LC) doubly-fed induction generator control program firmware manual [3AUA0000071689 (English)].
  • Page 30: Grid Codes

    30 System description Grid codes Grid codes specify static and dynamic requirements to be fulfilled by a wind power installation. Static requirements mainly determine the voltage control and power control during normal operation. Most of the recent grid codes include also power quality requirements such as harmonics distortion limits, flicker etc.
  • Page 31: Example Limit Curves

    System description 31 Example limit curves According to this example, electrical power network failure (eg, voltage dip/sag) may not cause instability above the limit line 1 or disconnection of the converter from the grid. The limit curves for voltage at the grid connection in case of a fault in the grid are shown below. U denotes the remaining grid voltage and U the converter nominal voltage.
  • Page 32: Grid Fault Ride-Trough Capability

    32 System description Grid fault ride-trough capability Although the advantage of doubly-fed concept is that the size of the wind turbine converter is significantly smaller than full-power converter, the drawback is that the rotor-side converter is a vulnerable part of the system. It has a restricted overcurrent limit and it needs special attention especially during faults in the grid.
  • Page 33 System description 33 Optional MCB3 MCB1 DC chopper ABRU (optional) MCB2 ACBU CONVERTER CTRL WIND TURBINE CTRL With the crowbar and the DC chopper, the wind turbine is capable of handling fault situations like rotor overspeed, short interruptions, voltage dips/sags and swells. With these energy absorbers, the converter is capable of meeting even the most strictest grid fault ride-through requirements in accordance with international grid codes.
  • Page 34: Grid Support

    Six different voltage levels can be defined. Examples of setting the grid support parameters are shown in the diagrams below. For further information, see ACS800-67(LC) doubly-fed induction generator control program firmware manual [3AUA0000071689 (English)].
  • Page 35: Grid Support Example

    System description 35 Grid support example  (p.u) grid 0.75 0.25 1.25 grid qref 32.23 GS AFTER DIP 32.24 GS TIME AFTER DIP...
  • Page 36: Stator Circuit Connection To Grid

    The hardware connection type for the grid connection is defined by parameter 16.20 GRID CONNECT MODE. For the time schemes of the grid connection signals and operation of digital inputs and outputs, see ACS800-67(LC) doubly-fed induction generator control program firmware manual [3AUA0000071689 (English)]. The differences between the configurations are presented below.
  • Page 37: Main Circuit Breaker (Par. 16.20 Grid Connect Mode Set To Mcb1+Mcb3/A)

    System description 37 Main circuit breaker (par. 16.20 GRID CONNECT MODE set to  MCB1+MCB3/A) The configuration below is used when the concept contains an optional grid-side breaker (MCB1). Turbine transformer MCB1 MCB3 MCB2 MCB1 main breaker MCB2 converter contactor MCB3 stator contactor Main circuit breaker (par.
  • Page 38: Stator Contactor (Par. 16.20 Grid Connect Mode Set To Mcb1+Mcb3/C)

    38 System description Stator contactor (par. 16.20 GRID CONNECT MODE set to  MCB1+MCB3/C) The configuration below is used when MCB1 and MCB3 are connected in series. Turbine transformer MCB1 MCB3 MCB2 MCB1 stator breaker MCB2 converter contactor MCB3 stator contactor The breaking device type for the grid connection is defined by parameter 20.27 CONT OPEN CUR.
  • Page 39: Grid Connection Procedure

    System description 39 Grid connection procedure  Turbine transformer MCB3 MCB2 A typical procedure required to connect the wind generator to the grid is as follows: • The system is operational if the rotor speed is in the predetermined normal operating range (eg, from 70% to 130% of the synchronous speed).
  • Page 40: Phasing Checks Executed At Start-Up

    40 System description Phasing checks executed at start-up During the encoder calibration and voltage synchronization, the software ensures that the grid, encoder, stator and rotor phasings are correct. The U-phase (and V- and W-phase) of the grid is connect to the U-phase of the stator via main circuit breaker. Commissioning phasing requirement Main circuit breaker Grid...
  • Page 41: Start-Up With Low Voltage Stator

    Start-up with low voltage stator 41 Start-up with low voltage stator What this chapter contains This chapter describes the basic start-up procedure of the wind turbine converter equipped with doubly-fed induction generator control program. Stator breaker Note: Grid-side converters are delivered with one of the following grid voltage measurement methods: •...
  • Page 42: How To Start-Up The Converter

    Safety  The start-up may only be carried out by a qualified electrician. The safety instructions must be followed during the start-up procedure. See ACS800-67 wind turbine converters for asynchronous slip ring generators hardware manual [3AFE68392454 (English)]. Check the installation. See the installation checklist in the converter hardware manual.
  • Page 43 E = stator voltage without losses (on the generator data sheet) U = stator voltage (on the generator name plate). The rotor resistance 99.25 R (R2PH on the ABB generator equivalent circuit data) reduced to the stator reference frame is calculated with the following equation:...
  • Page 44 50.04 PULSE NR Select the communication profile used by the converter. For more 16.11 COMM PROFILE information see section ABB Drives communication profile on page Set parameter limits in group 20 LIMITS according to the process 20.05 USER POS TORQ requirements.
  • Page 45: Time Setting

    Start-up with low voltage stator 45 Time setting  Set rotor-side converter 16.01 PARAM LOCK to OFF. 16.01 PARAM LOCK Set the date and time as follows: • Set parameter 95.07 RTC MODE value to SET. 95.07 RTC MODE • Check/adjust the date and time by parameters 95.01…95.06. 95.01…95.06 •...
  • Page 46 46 Start-up with low voltage stator NUIM board in use (grid-side converter control program IXXR72xx): • Enable the grid-side converter parameter lock by setting parameter 16.03 PASS CODE 16.03 PASS CODE to 2303. Parameter groups 100…202 become visible when the parameter lock is enabled. NAMU / BAMU board in use (grid-side converter control program IWXR74xx): •...
  • Page 47 Note: If this test fails, grid-side converter grid voltage cabling must be checked. See the converter hardware manual. Check the grid-side converter parameters. See the grid-side converter parameter list in ACS800-67(LC) doubly-fed induction generator control program firmware manual [3AUA0000071689 (English)].
  • Page 48: Grid-Side Converter And Dc Chopper Test

    Set the Low Voltage Ride Through function and Grid Support function Grid support function can parameters. Values must be set according to the selected grid code. be tuned by parameters in See ACS800-67(LC) doubly-fed induction generator control program group 32 LV RIDE- firmware manual [3AUA0000071689 (English)]. THROUGH.
  • Page 49 Start-up with low voltage stator 49 Set parameter 30.13 DI7 EXT EVENT to NO. (grid-side converter 30.13 DI7 EXT EVENT par.) Test that the DC chopper FAULT signal trips the converter. Check that 690 V is disconnected and DC voltage is 0 V. Check ABRC-65 board settings: S1 = 2 S2 = 7...
  • Page 50: Rotor-Side Converter Test

    WRONG GRID DIR GRID SYNC FAILED WRONG ROTOR PHASING Monitor the most important signals as explained below. For the possible causes and remedies, see ACS800-67(LC) doubly- fed induction generator control program firmware manual [3AUA0000071689 (English)]. If everything is in order, the doubly-fed induction generator control...
  • Page 51: Stator Voltage Synchronization Test

    Start-up with low voltage stator 51 It is useful to record important signals with the DriveWindow monitoring PC tool. 01.01 MOTOR SPEED [rpm] 01.10 DC VOLTAGE [V] 01.11 MAINS VOLTAGE [V] 02.01 STATOR IS [RMS] 02.02 STATOR VOLTAGE [V] 02.06 ROTOR IR [RMS] The figure below shows a typical start in local mode.
  • Page 52 52 Start-up with low voltage stator The following figure represent synchronization at 1300 rpm speed (under speed synchronization). 06.08 STATOR Y FLUX is synchronized to 06.06 GRID Y FLUX and 06.07 STATOR U FLUX is synchronized to 06.06 GRID U FLUX.   &KDQQHO ...
  • Page 53: Start-Up Of The Air Damper

    The function opens the damper again when the converter restarts and its temperature rises high enough. See also Doubly-fed induction generator control program for ACS800-67(LC) wind turbine converters firmware manual [3AUA0000071689 (English)].
  • Page 54: Final Settings

    54 Start-up with low voltage stator Set parameter 15.06 ANALOGUE OUTPUT 2 to 112. 15.06 ANALOGUE OUTPUT 2 Check that all temporary installations are removed. Close the door of the sliding frame. Close FF005. Switch the converter to Local control mode. Start the converter at zero speed.
  • Page 55: Start-Up With Medium Voltage Stator

    Start-up with medium voltage stator 55 Start-up with medium voltage stator What this chapter contains This chapter describes the medium voltage start-up procedure of the wind turbine converter equipped with doubly-fed induction generator control program. 12 kV 690 V Note: Grid-side converters are delivered with one of the following grid voltage measurement methods: •...
  • Page 56: How To Start-Up The Converter

    Safety  The start-up may only be carried out by a qualified electrician. The safety instructions must be followed during the start-up procedure. See ACS800-67 wind turbine converters for asynchronous slip ring generators hardware manual [3AFE68392454 (English)]. Check the installation. See the installation checklist in the converter hardware manual.
  • Page 57 E = stator voltage without losses (on the generator data sheet) U = stator voltage (on the generator name plate). The rotor resistance 99.25 R (R2PH on the ABB generator equivalent circuit data) reduced to the stator reference frame is calculated with the following equation:...
  • Page 58: Time Setting

    50.04 PULSE NR Select the communication profile used by the converter. For more 16.11 COMM PROFILE information see section ABB Drives communication profile on page Set parameter limits in group 20 LIMITS according to the process 20.05 USER POS TORQ requirements.
  • Page 59: Grid-Side Converter And Crowbar Test

    Start-up with medium voltage stator 59 Grid-side converter and crowbar test  Communication between the grid-side converter and the rotor-side converter is checked by controlling the grid-side converter unit via the rotor-side converter unit parameters. Set parameter 21.01 ISU LOCAL CTR WORD to 9 (hex), ie, 1001 21.01 ISU LOCAL CTR (bin): grid-side converter starts charging the DC capacitors, closes WORD...
  • Page 60 60 Start-up with medium voltage stator NUIM board in use (grid-side converter control program IXXR72xx): • Enable the grid-side converter parameter lock by setting parameter 16.03 PASS CODE 16.03 PASS CODE to 2303. Parameter groups 100…202 become visible when the parameter lock is enabled. NAMU / BAMU board in use (grid-side converter control program IWXR74xx): •...
  • Page 61 FLUX Y ACT signals are in phase, the flux measurement is OK. Note: If this test fails, grid-side converter grid voltage cabling must be checked. See the converter hardware manual. Check the grid-side converter parameters. See ACS800-67(LC) doubly-fed induction generator control program firmware manual [3AUA0000071689 (English)].
  • Page 62: Rotor-Side Converter Test

    Set the Low Voltage Ride Through function and Grid Support function Grid support function can parameters. Values must be set according to the selected grid code. be tuned by parameters in See ACS800-67(LC) doubly-fed induction generator control program group 32 LV RIDE- firmware manual [3AUA0000071689 (English)]. THROUGH.
  • Page 63: Stator Voltage Synchronization Test

    WRONG GRID DIR GRID SYNC FAILED WRONG ROTOR PHASING Monitor the most important signals as explained below. For the possible causes and remedies, see ACS800-67(LC) doubly- fed induction generator control program firmware manual [3AUA0000071689 (English)]. If everything is in order, the doubly-fed induction generator control program continues to identify the generator magnetizing reactance.
  • Page 64 64 Start-up with medium voltage stator Start the DriveWindow datalogger. Start the rotor-side converter with the DriveWindow START button. The following figure presents synchronization at 1300 rpm speed (under speed synchronization). 06.08 STATOR Y FLUX is synchronized to 06.06 GRID Y FLUX and 06.07 STATOR U FLUX is synchronized to 06.06 GRID U FLUX.
  • Page 65: Start-Up Of The Air Damper

    The function opens the damper again when the converter restarts and its temperature rises high enough. See also Doubly-fed induction generator control program for ACS800-67(LC) wind turbine converters firmware manual [3AUA0000071689 (English)].
  • Page 66: Final Settings

    66 Start-up with medium voltage stator Set parameter 15.06 ANALOGUE OUTPUT 2 to 112. 15.06 ANALOGUE OUTPUT 2 Check that all temporary installations are removed. Close the door of the sliding frame. Close FF005. Switch the converter to Local control mode. Start the converter at zero speed.
  • Page 67: Starting Sequence

    Start-up with medium voltage stator 67 Starting sequence The following figures present the starting sequences for the ABB drives profile and the Profile B. (Profile is selected by parameter 16.11 COMM PROFILE.) Terms and abbreviations used in the figures: Term/Abbreviation...
  • Page 68 68 Start-up with medium voltage stator ABB Drives profile Start command X2: 1-2 Cabinet temperature and humidity OK Heating ON Auxiliary power ON Booting time Fieldbus comm. starts Discharged DC voltage (ISU-INU) ISU contactor ISU modulation INU modulation Synchr. to grid...
  • Page 69 Start-up with medium voltage stator 69 Profile B Start command X2: 1-2 Cabinet temperature and humidity OK Heating ON Auxiliary power ON Booting time Fieldbus comm. starts Discharged DC voltage (ISU-INU) ISU contactor ISU modulation INU modulation Syncr. to grid Grid connection Grid connected Stop sequence...
  • Page 70: Start-Up Measurements

    70 Start-up with medium voltage stator Start-up measurements The start-up measurements described in this section give useful information if a problem is detected during the start-up. These measurements are not normally required during the start-up procedure. WARNING! The safety instructions must be followed during start-up procedure. See the converter hardware manual for safety instructions.
  • Page 71 Start-up with medium voltage stator 71 21.07 BATTERY TEST is set to CONNECT BATT 67$725 ,8 > 67$725 ,< > @ Phase U current transformer polarity check: • +1.5 V is connected to X1:1 of the NUIM-6x unit and • -1.5 V is connected to X1:2 of the NUIM-6x unit.
  • Page 72: Phase W Test

    72 Start-up with medium voltage stator Phase W test 21.07 BATTERY TEST is set to NO            ,WHP  06 67$725 ,8 > @ ,WHP  06 67$725 ,< > @ 21.07 BATTERY TEST is set to CONNECT BATT 06.01 STATOR IU [%] 06.02 STATOR IY [%]...
  • Page 73: Test At Zero Speed

    Start-up with medium voltage stator 73 06.01 STATOR IU is zero. 06.02 STATOR IY measures negative values. Absolute values are higher than with the phase U test. Note: Values depend on the battery voltage and current transformer transformation ratio. Note: When battery is removed, the signals behaves in the opposite way. Test at zero speed ...
  • Page 74: Start In Local Control Mode

    74 Start-up with medium voltage stator Start in local control mode  It is useful to record important signals with the DriveWindow PC tool when the wind turbine converter is connected to the grid. The figure below represents a typical start in local mode.
  • Page 75: Voltage And Current Waveform Examples

    Start-up with medium voltage stator 75 Voltage and current waveform examples  The following figures represent the grid voltage, stator current and rotor current waveforms with nominal load and without load in the oversynchronization region. With nominal load 06.02 STATOR IY [%] 06.05 ROTOR IU [%] 06.07 STATOR U FLUX [%] 0.01...
  • Page 76 76 Start-up with medium voltage stator...
  • Page 77: Practical Examples

    For descriptions of the fieldbus connections, refer to • ACS800 IGBT supply control program firmware manual [3AFE68315735 (English)] • ACS800 grid-side control program firmware manual [3AUA0000075077 (English)] • ACS800-67(LC) doubly-fed induction generator control program firmware manual [3AUA0000071689 (English)] • fieldbus adapter manuals.
  • Page 78: Entering Start-Up Data And Torque Settings

    78 Practical examples Entering start-up data and torque settings Calculating/setting the motor nominal torque  You need • the DFIG data sheets from the generator supplier for the DFIG of the wind turbine that contain • rated (nominal) values • DFIG equivalent circuit (from stator side, in star connection) •...
  • Page 79: Stator Current And Voltage Measurement

    Practical examples 79 Stator current and voltage measurement NUIM-6x voltage measurement  Voltages U1,V1 and W1 are measured at both sides of the stator circuit breaker/contactor(s). The 690 V AC grid voltage is connected to the Voltage and Current Measurement unit (NUIM). Stator flux is measured through a low pass filter which has different time constants for 690 V AC and 575 V AC.
  • Page 80 80 Practical examples shown below. In this example the parameter 16.20 GRID CONNECT MODE is set to MCB1+MCB3/B. P1,K P2,L S1,k S2,l MCB1 MCB3 P1,K P2,L S1,k S2,l Optional NUIM NDCU MCB2 DFIG The maximum measurable stator current must be set by a parameter. The value is calculated with the following equation: 4,5 V ⋅...
  • Page 81: Generator Data

    Practical examples 81 Generator data Generator rating plate equivalent circuit parameters  The equivalent circuit of the generator is shown below. Note that the equivalent circuit is to be are derived looking from the stator-side ie, the voltages and currents are reflected on the stator-side.
  • Page 82 82 Practical examples Generator data Parameter Transformation ratio between the 99.15 MOTOR OPEN CKT V stator and the rotor. Defined when Note: Rotor open-circuit voltage. rotor shaft is mechanically locked and nominal stator voltage is fed to the stator windings. Long time rotor current limitation 99.16 MOTOR NOM IM Note: I...
  • Page 83: Parameters Of Parameter Group 99

    Practical examples 83 Parameters of parameter group 99  Parameter Description Source Description 99.02 MOTOR NOM Defines the nominal Rated stator voltage in VOLTAGE generator voltage. data sheet 99.03 MOTOR NOM Defines the nominal Rated stator current in The value is for information CURRENT generator stator-side data sheet...
  • Page 84: Parameter 99.05 Motor Nom Speed

    84 Practical examples Parameter Description Source Description 99.24 XM Defines the mutual Mutual reactance DFIG characteristics value inductance. of equivalent circuit 99.25 Rr Defines the rotor Rotor resistance (R ) of DFIG characteristics value resistance, which is equivalent circuit reduced to the stator side. 99.27 MAX MEAS Defines the maximum For an integrated power...
  • Page 85: Generator Nominal Power Calculation

    Practical examples 85 Generator nominal power calculation  Generator values must be given at 50 Hz (60 Hz). These values are not equal to the wind turbine nominal values. Wind turbine nominal power is achieved with 100% torque reference at the nominal wind turbine speed. Calculate the generator nominal power with the following equation.
  • Page 86: Mutual Inductance Xm And Rotor Resistance Rr Calculations

    99.24 XM · 99.16 MOTOR NOM IM The rotor resistance R (rotor-side converter parameter 99.25 Rr) reduced to the stator reference frame (R2PH on the ABB generator equivalent circuit data) is calculated with the following equation: R2PH 99.25 Rr 99.15 MOTOR OPEN CKT V 99.02 MOTOR NOM VOLTAGE...
  • Page 87: Current Measurement Of The Grid-Side Converter

    Practical examples 87 Current measurement of the grid-side converter The main circuit of the grid-side converter is shown below. Current is fed to the LCL filter to compensate the capacitors in no-load situations when current at the input to the converter (point a) is zero.
  • Page 88: Example

    88 Practical examples Example  ABB wind turbine generator 3.05 MW, stator voltage 12 kV, 60 Hz Generator type code AML 630L6A BAFT Generator type Slip ring generator Mounting designation IM 1001 Protected by enclosure/slip ring unit IP 54/23 Method of cooling...
  • Page 89 Practical examples 89 AML 630L6A BAFT Equivalent circuit corresponding to star connection Running Par. 99.21 Stator resistance R (120 °C) 0.42756 ohm Par. 99.22 Stator reactance X 4.4324 ohm Par. 99.24 Magnetizing reactance X 177.59 ohm Starting Stator resistance R (60 °C) 0.39143 ohm Stator reactance X...
  • Page 90: Abb Drives Communication Profile

    Calculated ABB Drives communication profile The following sections show control sequence examples using the ABB Drives communication profile. The Main Control Word (MCW) is the principal means of controlling the converter from WTC. The Control Word is sent to the converter by the WTC. The converter switches between its states according to the bit-coded instructions of the Control Word.
  • Page 91: Fault Sequence, Profile B

    Practical examples 91 Fault sequence, profile B  An example of the control sequence after a fault situation is described below. Step Command Description 8.10 CCU STATUS WORD bits after command 7.01 MAIN / end state CONTROL WORD b13 b12 b11 b10 b9 RUN=1 Device is running.
  • Page 92: Starting Sequence When The Grid-Side Converter Is Started First Separately

    92 Practical examples Starting sequence when the grid-side converter is started first  separately ABB Drives profile Start command X2: 1-2 Cabinet temperature and humidity OK Heating ON Auxiliary power ON Booting time Fieldbus comm. starts Discharged DC voltage (ISU-INU)
  • Page 93: Normal Start And Stop Sequence, Abb Drives Profile

    OFF speed. Datasets The datasets used for transmitting and receiving actual signals and parameters are shown in ACS800-67(LC) doubly-fed induction generator control program firmware manual [3AUA0000071689 (English)]. Fieldbus signals For signals used in the software interface with a specific fieldbus, refer to the software...
  • Page 94: Configuring The Neta-01 Ethernet Adapter Module

    94 Practical examples Configuring the NETA-01 Ethernet Adapter Module Configure the NETA-01 Ethernet Adapter Module as follows: 1. Follow instructions given in chapter Quick start-up guide in NETA-01 Ethernet adapter module user’s manual [3AFE64605062 (English)] to connect to the module. The instruction on setting the IP address is given below.
  • Page 95 Practical examples 95 3. Access the Configuration menu. 4. Open the Drives tab and click the Find drives button. Make sure that the Issue channel address check box is ticked. 5. Change the State field of the activated converters from FBA DSET to FBA DSET10 and give appropriate names to the converters in the Name fields.
  • Page 96: Creating A Full Backup Package And Saving It In .Bpg Format

    96 Practical examples Converters with one rotor-side converter and one grid-side converter Creating a full Backup Package and saving it in .BPG format While creating a Backup Package, the converter must be in remote control (not controlled from the DriveWindow). Make a Backup Package with DriveWindow separately from each converter as follows: 1.
  • Page 97: Backup Package

    Practical examples 97 Backup Package  A Backup Package is similar to a Loading Package. It is a single PC file with a filename extension of .BPG. A Backup Package can be opened, saved, saved with a new name and closed. Backup and restore commands can be performed only if a Backup Package is open.
  • Page 98: Restoring A Backup File Into The Rdcu Or Ndcu Board

    98 Practical examples Restoring a backup file into the RDCU or NDCU board Restore a backup file into the RDCU or NDCU board as follows: 1. Select from the File menu System Software / Open command. 2. In the Open box, select the backup package and press Open. 3.
  • Page 99 Practical examples 99...
  • Page 100: Saving A Parameter File (.Dwp) To The Pc

    100 Practical examples Saving a parameter file (.dwp) to the PC Save a parameter file to the PC with DriveWindow as follows: 1. Select the converter. 2. From the File menu, select Parameters / Save as command. If the command is disabled (gray), press the Drive / Take Control button (a).
  • Page 101: Downloading Parameters Into The Converter

    4. Tick “Restore user data (10…98)” for the restore type. Press OK. Note: Set parameters into group 99 manually afterwards. 5. If you are sure to proceed, press Yes. If Version conflict info appears, contact ABB. Note: After downloading, check the parameters of groups 56 and 58 if an Adaptive Program is in use.
  • Page 102: Updating The Firmware

    102 Practical examples Updating the firmware 1. Before updating the firmware it is recommended to create a full Backup Package of the old firmware in RDCU and NDCU boards and save the old parameter file. For details, see sections Creating a full Backup Package and saving it in .BPG format Saving a parameter file (.dwp) to the 2.
  • Page 103: Communication Parameter Settings

    Set according to power type. 4116 See also section NUIM-1x and 4939 NUIM-6x current 6585 measurements on page 79. 6585 In addition, the fieldbus module settings must be made. See the ACS800-67(LC) doubly- fed induction generator control program firmware manual [3AUA0000071689 (English)].
  • Page 104: Grid-Side Converter

    104 Practical examples Grid-side converter Name Factory setting 11.02 Q REF SELECT 2402 70.04 CH0 TIMEOUT 2000 ms (When parameter is set to zero, time is not monitored.) 70.15 CH3 NODE ADDR 70.20 CH3 HW CONNECTION RING 71.01 CH0 DRIVEBUS MODE 90.01 D SET 10 VAL 1 90.02...
  • Page 105: Changing The Rotation Direction Of The Generator

    General  Terminal markings of the ABB generators for the stator (U, V, W) and rotor (K, L, M) are based on IEC 60034-8. The terminal markings are arranged so that the clockwise rotation is obtained when the alphabetical sequence of the letters (for example U1, V1, W1) corresponds to the time sequence of the system phase voltages.
  • Page 106: Counterclockwise Rotation At Drive End (D End)

    106 Practical examples Counterclockwise rotation at drive end (D end)  Power cabinet Encoder...
  • Page 107: Downloading The Diagnostics Of Apbu Branching Unit

    Practical examples 107 Downloading the diagnostics of APBU branching unit APBUDL is a tool program for APBU datalogger control and data upload. It is highly recommended to use the APBUDL program with the RUSB-01 adapter. With following instructions the datalogger file is downloaded for further analysis. Program file is APBUDL.exe.
  • Page 108: Setting The Parameters According To Grid Code

    108 Practical examples Setting the parameters according to grid code Parameter setting examples in cases of Spanish, Italian and United Kingdom grid codes are given below. Spanish grid code  Parameter Setting Control program AJXC2330 (or newer) parameters: 30.05 AC OVERVOLT TRIP 793.5 V 30.06 AC UNDERVOLT TRIP 68.9999 V...
  • Page 109: Italian Grid Code

    Practical examples 109 Italian grid code  Parameter Setting Control program AJXC2330 (or newer) parameters: 4.04 DEVICE ID INU 800 1160_7NC 20.23 USER KVAR LIMIT 100% 30.05 AC OVERVOLT TRIP 30.06 AC UNDERVOLT TRIP (2) (V) 30.07 AC OVERFREQ TRIP 53 Hz 30.08 AC UNDERFREQ TRIP 47 Hz...
  • Page 110 110 Practical examples Parameter Setting 32.35 PRIORITY t<t4 Iq > Ip 32.36 PRIORITY t>t4 Iq > Power 32.37 P/Q UNSYM DIS 32.38 P/Q UNSYM ENA 32.41 ENVELOPE PAR SEL PAR 2 32.66 RT OF LEVEL1 51.5 32.67 RT OFTIME1 32.68 RT OF LEVEL2 51.5 32.69 RT OF TIME2 32.70 RT OF LEVEL3...
  • Page 111: Uk Grid Code

    Practical examples 111 UK grid code  Parameter Setting Control program AJXC2330 (or newer) parameters: 30.03 EARTH FAULT LEVEL 30.04 STATOR CURR TRIP 30.05 AC OVERVOLT TRIP 793.5 V 30.06 AC UNDERVOLT TRIP 30.07 AC OVERFREQ TRIP 53 Hz 30.08 AC UNDERFREQ TRIP 47 Hz 32.01 GRID SUPPORT MODE MAX.
  • Page 112 112 Practical examples Parameter Setting 32.38 P/Q UNSYM ENA Control program IWXR7300 (or newer) parameters: 40.01 RT ENABLE 40.02 NAMU BOARD ENABLE 40.04 PHASE MEAS ENA 40.05 UAC CTRL SEL RMS VOLTAGE 40.09 RT U/Un MOD STOP 9.99999% 40.10 RT U/Un LEVEL1 40.11 RT U/Un LEVEL2 40.12 RT U/Un LEVEL3 40.13 RT U/Un DELTA t1...
  • Page 113: Tracing The Source Of Warnings, Limits And Faults

    Tracing the source of warnings, limits and faults 113 Tracing the source of warnings, limits and faults What this chapter contains This chapter describes the warnings, limits and faults of the converter and refers to descriptions of the warning and fault messages and LEDs given in other manuals. Warnings Abnormal statuses are indicated by the warning words and messages.
  • Page 114: Faults

    Further information on page 12. Warning and fault messages Refer to • ACS800 IGBT supply control program firmware manual [3AFE68315735 (English)] • ACS800 grid-side control program firmware manual [3AUA0000075077 (English)] • ACS800-67(LC) doubly-fed induction generator control program firmware manual [3AUA0000071689 (English)].
  • Page 115: Checking The Phase Sequence Of Grid-Side Converter Voltage Measurement

    Tracing the source of warnings, limits and faults 115 Checking the phase sequence of grid-side converter voltage measurement NUIM board in use (grid-side converter control program IXXR72xx)  If an OVERCURRENT fault occurs during the start-up when the operation of the converter is tested, or if the grid fault ride-through function fails, make the checks described in the table below.
  • Page 116: Namu / Bamu Board In Use (Grid-Side Converter Control Program Iwxr74Xx)

    116 Tracing the source of warnings, limits and faults NAMU / BAMU board in use (grid-side converter control program  IWXR74xx) If an OVERCURRENT fault or GRID SYNC FAIL fault occurs during the start-up when the operation of the converter is tested, or if the grid fault ride-through function fails, make the checks described in the table below.
  • Page 117: Faults In Measurements

    Tracing the source of warnings, limits and faults 117 Faults in measurements Fault Cause What to do Pulse encoder pulses or zero Generator overcurrent If the encoder is of unisolated type, check that the pulse are missing or wrong fault cable is grounded only on converter side.
  • Page 118 118 Tracing the source of warnings, limits and faults...
  • Page 119: Product And Service Inquiries

    Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
  • Page 120 Contact us www.abb.com/windconverters 3AUA0000095094 Rev B (EN) 2017-12-31...

Table of Contents