16 **
DC BUS RIPPLE
17
UNDERLOAD
18
19
DDCS LINK
20 - 26 **
HARDWARE ERROR
Full display blinking (ACS100-PAN)
"COMM LOSS" (ACS-PAN)
** Note! These faults are indicated by a red blinking LED and are reset by turning the power off for a
while.
ACS 400 User's Manual
Ripple voltages on the DC bus are too large.
Mains phase may be missing
Fuse may be blown
Motor load is too low. Check for a problem in the driven equipment.
Refer to parameters 3013 – 3015.
Reserved
Problem with DDCS link.
Check the DDCS option module and the optic fibres.
Check the status of the fieldbus adapter. Refer to appropriate
fieldbus adapter manual.
Check connections between external control system and fieldbus
adapter.
Alternatively, check the status of the IO extension modules (NDIO),
required by PFC block.
Refer also to "DDCS Option Module Manual" and parameters 5004 –
5007.
Hardware error. Contact supplier.
Serial link failure. Bad connection between the control panel and the
ACS 400.