Group 81: PFC Control

Parameters for Pump-Fan Control (PFC). Appendix B gives detailed information on PFC. Chapter
Application Macros describes the default signal connections.
Code Description
8103 REFERENCE STEP 1
Sets a percentage value that is added to the process reference when at least one auxiliary (constant speed)
motor is running. Default value is 0 %.
Example: An ACS 400 operates three parallel pumps that pump water to a pipe. The pressure in the pipe is
controlled. The constant pressure reference is set by parameter 4020
At low water consumption level only the speed regulated pump is run. When water consumption increases,
constant speed pumps are started; first one pump, and if the demand is still growing, also the other pump.
When water flow increases, the pressure loss increases between the beginning (measurement site) and the
end of the pipe. By setting suitable reference steps (parameters 8103
REFERENCE STEP
reference steps compensate the growing pressure loss and prevent the pressure fall at the end of the pipe.
8104 REFERENCE STEP 2
Sets a percentage value that is added to the process reference when at least two auxiliary (constant speed)
motors are running. Default value is 0 %. See parameter 8103
8105 REFERENCE STEP 3
Sets a percentage value that is added to the process reference when at least three auxiliary (constant
speed) motors are running. Default value is 0 %. See parameter 8103
8109 START FREQ 1
Sets a frequency limit. See Figure 56 on page 106. When ACS 400 output frequency exceeds value (8109
1 + 1 Hz) and no auxiliary motors are running, the Start Delay counter is started. When the time
START FREQ
set with parameter 8115
1 - 1 Hz), the first auxiliary motor is started.
START FREQ
After the first auxiliary motor is started, ACS 400 output frequency is decreased by value (8109
1 - 8112
FREQ
LOW FREQ
Note! Start Frequency 1 should be within limits 8112
8110 START FREQ 2
Sets a frequency limit (see Figure 56 ). When ACS 400 output frequency exceeds value (8110
+ 1 Hz) and one auxiliary motor is running, the Start Delay counter is started. When the time set with
parameter 8115
2 - 1 Hz), the second auxiliary motor is started.
FREQ
After the second auxiliary motor is started, ACS 400 output frequency is decreased by value (8110
2 - 8113
FREQ
LOW FREQ
Note! Start Frequency 2 should be within limits 8113
8111
START FREQ 3
Sets a frequency limit (see Figure 56). When ACS 400 output frequency exceeds value (8111
+ 1 Hz) and two auxiliary motors are running, the Start Delay counter is started. When the time set with
parameter 8115
3 - 1 Hz), the third auxiliary motor is started.
FREQ
After the third auxiliary motor is started, ACS 400 output frequency is decreased by value (8111
3 - 8114
LOW FREQ
Note! Start Frequency 3 should be within limits 8114
8112 LOW FREQ 1
Sets a frequency limit (see Figure 56). When ACS 400 output frequency falls below value (8112
- 1 Hz) and one auxiliary motor is running, the Stop Delay counter is started. When the time set with
parameter 8116
1 + 1 Hz), the first auxiliary motor is stopped.
After the auxiliary motor is stopped, ACS 400 output frequency is increased by value (8109
8112
LOW FREQ
Note! Low Frequency 1 should be within limits 2007
ACS 400 User's Manual
2) the process reference is increased along the increasing pumping capacity. The
AUX MOT START D
1).
is elapsed and if the output frequency is still above value (8110
AUX MOT START D
2).
is elapsed and if the output frequency is still above value (8111
AUX MOT START D
3).
. is elapsed and if the output frequency is still below value (8112
AUX MOT STOP D
1).
REFERENCE STEP
is elapsed and if the output frequency is still above value (8109
1 and 2008
LOW FREQ
2 and 2008
LOW FREQ
3 and 2008
LOW FREQ
MINIMUM FREQ
.
INTERNAL SETPNT
1 and 8104
REFERENCE STEP
1
1.
REFERENCE STEP
MAXIMUM FREQ
MAXIMUM FREQ
MAXIMUM FREQ
+1 and 8109
START FREQ
START
-1.
2
START FREQ
START
START
-1.
3
START FREQ
START
START FREQ
-1.
1
LOW FREQ
LOW FREQ
1 -
START FREQ
1.
105