Reference Sections

A Environment for Storage, Transportation and Stationary Use
Table 1
ACS 400
Installation Site Altitude
Ambient Temperature
Relative Humidity
Contamination Levels
(IEC 721-3-3)
Atmospheric Pressure
Sinusoidal Vibration
(IEC-60068-2-6)
Shock
(IEC 68-2-29)
Free Fall
ACS 400 User's Manual
Stationary Use
• 0...1000 m if P
and I
N
• 1000...2000 m if P
and I
N
derated 1% every 100 m above
1000 m
• 0...40 °C
• max. 50 °C if P
and I
N
to 90%
< 95% (non-condensing)
No conductive dust allowed.
The ACS 400 should be installed in clean air according to IP classification.
Cooling air must be clean, free from corrosive materials and electrically conduc-
tive dust.
In UL installations the ACS 400 should be installed in clean and dry air, free from
dripping water.
• chemical gases: Class 3C2
• solid particles: Class 3S2
• 2-9 Hz 0.3 mm
2
• 9-200 Hz 2 m/s
not allowed
not allowed
Storage and Transportation
in the protective package
-
100%
2
2
-40...+70 °C
derated
2
Storage
• chemical gases: Class 1C2
• solid particles: Class 1S3
Transportation
• chemical gases: Class 2C2
• solid particles: Class 2S2
Storage
• 2-9 Hz 1.5 mm
• 9-200 Hz 5 m/s
Transportation
• 2-9 Hz 3.5 mm
• 9-200 Hz 10 m/s
• max. 100 m/s
• 76 cm (30 in.), frame size R1
• 61 cm (24 in.), frame size R2
• 46 cm (18 in.), frame size R3
• 31 cm (12 in.), frame size R4
2
2
2
2
(330 ft./s
), 11 ms
3