Group 32: Supervision - ABB ACS 400 User Manual

Frequency converter from 2.2 to 37 kw
Hide thumbs Also See for ACS 400:
Table of Contents

Advertisement

Group 32: Supervision

Parameters of this group are used together with relay output parameters 1401
1402
RELAY OUTPUT
supervised. Relays can be configured to be energised when the values of supervised parameters are
either too low or too high.
Code Description
3201 SUPERV 1 PARAM
First supervised parameter number of the Operating Data group (Group 01).
3202 SUPERV 1 LIM LO
First supervision limit low. Display of this parameter depends on selected supervised parameter (3201).
3203 SUPERV 1 LIM HI
First supervision limit high. Display of this parameter depends on selected supervised parameter (3201).
3204 SUPERV 2 PARAM
Second supervised parameter number of the Operating Data group (Group 01).
3205 SUPERV 2 LIM LO
Second supervision limit low. Display of this parameter depends on selected supervised parameter (3204).
3206 SUPERV 2 LIM HI
Second supervision limit high. Display of this parameter depends on selected supervised parameter (3204).
De-energised = 0
De-energised = 0
A = Parameter 1401
value is
B = Parameter 1401
value is
Figure 51 Operating data supervision using relay outputs.
90
2. Any two parameters of the Operating Data group (Group 1) can be
hi (3203)
lo (3202)
Energised = 1
Energised = 1
RELAY OUTPUT
1
or
SUPRV
OVER
RELAY OUTPUT
1
or
SUPRV
UNDER
Value of supervised parameter
1 (1402
RELAY OUTPUT
2
SUPRV
OVER
1 (1402
RELAY OUTPUT
2
SUPRV
UNDER
RELAY OUTPUT
A
B
2)
2)
ACS 400 User's Manual
1 and

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents