Bosch AMAX 2100 Installation Manual page 144

Hide thumbs Also See for AMAX 2100:
Table of Contents

Advertisement

144
en | Troubleshooting
1.
2.
P
RF Receiver 1 Missing
Condition:
1.
2.
Restore:
4
Supervise:
1.
2.
P
RF Receiver 1 Jammed
Condition:
A signal is disturbing the receiver if a wireless module is enabled.
Restore:
4
Supervise:
1.
2.
P
RF Sensor Missing
Condition:
A wireless zone sends no status report to the receiver in the RF supervision interval if a
wireless module is enabled.
Restore:
4
Supervise:
1.
2.
P
RF Sensor Fault
Condition:
A wireless zone is in an abnormal condition (e.g. Remove the pyro from the smoke
detector/...) and a wireless module is enabled.
Restore:
2014.11 | 02 | F.01U.267.112
Report the receiver fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off, when there is no other system fault.
No communication with receiver available if a wireless module is enabled.
A RF zone, repeater or keyfob is configured, but the wireless module is disabled.
Restore the communication with the receiver to a normal condition, enable the wireless
module and reset the fault. For more information, refer to RF Devices, page 78.
Report the receiver missing fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
Remove the disturbing signal around the receiver, enable the wireless module and reset
the fault. For more information, refer to RF Devices, page 78.
Report the receiver jam fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
RF Sensor Failure
Make sure that all wireless zones are sending status reports to the receiver in the RF
supervision interval and reset the fault. For more information, refer to RF Devices, page
78.
Report the wireless zone missing fault to configured destination when the fault is
detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
Installation Guide
AMAX 2100 / 3000 / 4000