Bosch AMAX 2100 Installation Manual page 146

Hide thumbs Also See for AMAX 2100:
Table of Contents

Advertisement

146
en | Troubleshooting
Supervise:
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
4
P
2 - Power Failure
Condition:
1.
2.
3.
Restore:
1.
2.
Supervise:
1.
2.
P
Condition:
1.
2.
Restore:
1.
2.
Supervise:
1.
2.
3.
P
Condition:
The Aux power supply voltage is lower than 9V.
Restore:
4
Supervise:
1.
2.
2014.11 | 02 | F.01U.267.112
Reset the fault.
The FAULT indicator is turned off when there is no other system fault.
Panel AC Failure
AC supply deficiency caused by a transformer.
Power supply fuse is broken (230V).
Power supply is disconnected (230V).
Reconnect the AC supply and reset the fault. For more information refer to Installation,
page 25.
Monitor the voltage by MPU.
If the AC supply is not restored one hour after the fault occurred, report the fault to
configured destination on address 124.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the AC supply is reconnected, the MAINS indicator lights up (except in
programming mode or in code functions mode).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
Battery Low Battery
The battery voltage is lower than 11V+-1%.
No battery is connected.
Connect a battery. For more information, refer to Battery Installation, page 26.
Raise battery voltage to 12V+-1%, perform a dynamic battery test (time set in
programming address 204) and reset the fault.
Set the system to perform a dynamic battery test on a regular basis (time set in
programming address 204) and every time the system is armed or reset.
Report the low battery to the configured destination programmed on address 124.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
Panel Aux Power 1-2 Failure
Raise the voltage to 12V and reset the fault.
Monitor the voltage by MPU.
Report the AUX power fault to the configured destination programmed on address 124.
Installation Guide
AMAX 2100 / 3000 / 4000
Bosch Sicherheitsysteme GmbH

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amax 3000Amax 4000

Table of Contents