en | Address Programming
How to set the IP address and port number:
The IP address is programmed with the 17 digits: Digits 1 - 12 for the IP address of the
receiver and 13 - 17 for the port.
It is not necessary to enter dots in programming, but 0 must be entered ahead of the digit to
make up 3 digits when each IP address unit is fewer than 3 digits. 0 must be entered ahead of
the digit to make up 5 digits when the port is fewer than 5 digits.
Example:
Receiver IP address 128.73.168.7, port 7700, should be entered as the following: 128 073 168
007 07700
9.1.2

Reports Programming

System Reports
Option
Zone status restore report
AWAY arming / disarming report
STAY arming / disarming report
System status report (zone fail, comm. fail, telephone line
fail, AC fail, low battery and so on.)
Keypad panic alarm report
Keypad fire alarm report
Keypad medical alarm report
Automatic test report
0 = no report, 1 = receiver 1, 2 = receiver 2, 3 = receiver 3, 4 = receiver 4, 5 = receiver 1,2,3,
and 4, 6 = receiver 1 (2,3, and 4 for backup), 7 = receiver 1 (2 for backup) and receiver 3 (4
for backup)
Notice!
When the transmission format for receiver in the receiver programming is set to 0 (not used),
i.e. setting the report option as sending report to a receiver, then the AMAX panel will actually
not send any report.
Automatic Test Report
Option
Automatic test report time: interval
00 = Do not use timing report , 01 - 24 = 1 - 24 hours
Automatic report time: hour
00 - 99 = 0 - 99 hours, others = do not use real-time report
2014.11 | 02 | F.01U.267.112
Installation Guide
AMAX 2100 / 3000 / 4000
Address
Default
0120
6
0121
6
EN=1/5/6/7
0122
6
EN=1/5/6/7
0123
6
EN=1/5/6/7
0124
0
0125
0
0126
0
0127
6
EN=1/5/6/7
Address
Default
0128 – 0129
24
VDS-A
EN=1-24
0130 – 0131
99