Bosch AMAX 2100 Installation Manual page 143

Hide thumbs Also See for AMAX 2100:
Table of Contents

Advertisement

AMAX 2100 / 3000 / 4000
1.
2.
P
Module DX4010 Missing
Condition:
No communication with DX4010 if printer is available.
Restore:
4
Supervise:
1.
2.
P
Printer Missing
Condition:
No communication with the printer available, if the printer is enabled and the DX4010 is in a
normal condition.
Restore:
4
Supervise:
1.
2.
P
Printer Fault
Condition:
The printer condition is abnormal (e.g. printer no paper/printer buffer is overflow/...) if printer
is enabled and the DX4010 is in a normal condition.
Restore:
4
Supervise:
1.
2.
P
RF Receiver 1 Fault
Condition:
The receiver condition is abnormal (e.g. RF micro is removed/hold RF micro in reset/...) if a
wireless module is enabled.
Restore:
4
Supervise:
Bosch Sicherheitsysteme GmbH
Report the DX2010 fault to configured destination on address 140 when the fault is
detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off, when there is no other system fault.
Printer Failure
Restore the communication with DX4010 to a normal condition and reset the fault.
Report the DX4010 missing fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off, when there is no other system fault.
Restore the communication with the printer to a normal condition and reset the fault.
Report the printer missing fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off, when there is no other system fault.
Restore the printer to a normal condition and reset the fault.
Report the printer error to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 10 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off, when there is no other system fault.
RF Receiver Failure
Restore the communication with the receiver to a normal condition and reset the fault.
For more information, refer to RF Devices, page 78.