Synapse Installation Guide

Gateway and ATA Placement

You can place the Gateway or ATA on a tabletop, mount it into a standard 19-inch metal
rack, or wall mount it. The PSTN Gateway must be installed within three feet of the
building ground point. Install each device using the following instructions.

Rack Mounting

To mount the Gateway or ATA into a standard 19-inch rack:
1. Remove the two mounting brackets and six screws from the packing tissue.
2. Position a bracket at the front of the device and align the screw holes using the
locating indent.
3. Insert each of the three screws into the holes provided and tighten securely. Repeat
the process for the other bracket.
4. Position the chassis into the 19-inch metal rack.
5. Insert a top mounting screw (not included) in one side and turn it several turns to
establish support. Repeat for the other side.
6. Tighten the screws.
Installation
Locating Indent
30
Back to Contents