Zone Attributes 1

Attributes can be assigned to a zone to alter its operation i.e. a
Guard zone with the 'Access' attribute will allow the user to
walk past the detector without causing a 'Fault' during the exit
mode or an Intruder alarm during the entry mode.
Select attributes by pressing keys 1 to 8 (a letter on the
display means the attribute is selected, a Dot on the display
means the attribute is not selected).
The following attributes are available:
O - OMITTABLE
Zones with this attribute can be manually omitted.
Zones without this attribute cannot be manually omitted.
F - FORCE OMIT
Zones with this attribute will be omitted if they are not secure
at the end of the exit mode.
Zones without this attribute will cause an 'Arm Fail' if they are
not secure at the end of the exit mode.
1 - PART 1 OMIT
Zones with this attribute will be omitted when 'Part Arm 1' is
selected.
Zones without this attribute will respond as normal.
2 - PART 2 OMIT
Zones with this attribute will be omitted when 'Part Arm 2' is
selected.
Zones without this attribute will respond as normal.
3 - PART 3 OMIT
Zones with this attribute will be omitted when 'Part Arm 3' is
selected.
Zones without this attribute will respond as normal.
A - ACCESS
Zones with this attribute will not cause a 'Fault' during the exit
mode or an Intruder alarm during the entry mode. However, if
the zone is activated at any other time an Intruder alarm will
occur.
Zones without this attribute will respond as normal.
E - ENTRY/EXIT 2
Zones with this attribute will start the 'Entry Delay 2' timer for
the selected area when the area is part armed.
!
'Entry/Exit 1 or 2' zones with this attribute will become a
'Guard' zone for the duration of the 'Abort' timer if a zone
with the 'Guard' attribute activates and cause an alarm
(when the area is fully armed).
Zones without this attribute will respond as normal.
G - GUARD
Zones with this attribute will cause an Intruder alarm when the
area is part armed (this would normally be used on 'Entry/Exit
1 or 2' zone types).
!
When the area is fully armed, activation of a zone with
this attribute will cause any 'Entry/Exit 1 or 2' zone with
the Entry/Exit 2 attribute to become a 'Guard' zone for
the duration of the 'Abort' timer.
Zones without this attribute will respond as normal.
36

Zone Attributes 2

Select attributes by pressing keys 1 to 8 (a letter on the
display means the attribute is selected, a Dot on the display
means the attribute is not selected).
The following attributes are available:
D - DOUBLE KNOCK
Zones with this attribute will only cause an alarm if it is
activated twice within the 'Double Knock' time window or for
the duration of the time window.
Zones without this attribute will respond as normal.
B - BEAM PAIR
Zones with this attribute will only cause an alarm if two zones
(assigned to the same area) with this attribute are activated
within the 'Beam Pair' time window.
Zones without this attribute will respond as normal.
T - ON TEST
Zones with this attribute will not cause an alarm if activated
during the 'Soak Test Time' (see page 47 for details).
However, the system will record the event in the log and
indicate to the user that the zone has failed the test. A test
failure will NOT prevent the user from arming and will clear
when an Engineer code is entered.
Zones without this attribute will respond as normal.
A - ACTIVITY
Zones with this attribute will cause an activity fault to be
displayed at the time of arming if they have not been
activated during the 'Activity Delay' period. If 'Config. option
14' (see page 49 for details) has been set to 'Activity Fault
Bar' the system/area cannot be armed until the zone has
been activated (forced walk test).
Zones without this attribute will respond as normal.
R - RESET
Zones with this attribute will not be monitored during the
'Detector Reset' period i.e. when the exit mode is started and
power is removed from certain detectors (to reset them) the
'Fault' on the zone is ignored.
Zones without this attribute will be monitored as normal.
A - AUTO RE-ARM
Zones with this attribute will only re-arm at the end of the bell
duration providing that the 'Re-arm' limit has not been
reached (see page 51 for details). Once this limit has been
reached, the zone will lock out and not cause any further
Intruder alarms.
Zones without this attribute will always re-arm at the end of
the bell duration.
Q - QUICK RESPONSE.
The response time of the zones with this attribute is governed
by the 'Zone Loop' response Timer (see page 47 for details).
The response time of a zone without this attribute is fixed at
250mS.
E – ENGINEER ALARM
Zones with this attribute will cause an Intruder alarm when
activated if the engineer arms the system/area.
Zones without this attribute will not cause an Intruder alarm
when activated if the engineer arms the system/area.
Premier 640 Installation Manual