Commissioning And Troubleshooting; Commissioning; Trouble-Shooting - Texecom Premier 640 Installation Manual

Hide thumbs Also See for Premier 640:
Table of Contents

Advertisement

Commissioning and Troubleshooting

4. Commissioning and Troubleshooting

Commissioning

Once ALL connections have been made to the control panel
and power is ready to be applied, you should read this
section before continuing.
When applying power for the first time, the factory default
settings must be loaded. The default settings ensure that
the control panel software is reset and all programming
information is loaded into memory.
The factory default settings are loaded by applying power to
the control panel whilst at the same time, holding down the
Factory Default button.
To default the control panel, proceed as follows:
Connect the black battery lead to the negative (–)
terminal of the standby battery and the red battery lead to
the positive (+) terminal of the standby battery
Press and hold the Factory Default button
Press the battery kick-start button to connect the battery
and ensure that the green heartbeat light illuminates
After the heartbeat light has illuminated, let go of the
Factory Default button (the heartbeat light will continue
to flash whilst the factory default settings are being
loaded, this can take up to 30 seconds)
If the system goes into alarm, enter the default
Engineer code
!"#$
tone will stop
To access the Engineer Programming Menu, enter the
default Engineer code
Program the system as described in section 6
(Programming the Control Panel)
Perform a zone test as described on 94. Remember that
some powered detectors (e.g. PIR's and combined
technology detectors) take several minutes to warm up
and become operational
Test the internal sounder, external sounder and strobe as
described on page 95
Replace the lid and secure with the lid screw supplied
Press
followed by YES to leave the programming
&
menu, the system will return to normal
The display will be showing that there is a 'Mains Power
Off' condition. Switch on the AC mains supply to the
control panel
The normal banner message (if programmed) will now
be displayed
Installation is now complete and the system is
ready for use.
28
, and the alarm
!"#$

Trouble-Shooting

Control Panel
No Power to unit (mains only)
Check the mains block fuse and replace if blown
Check for loose wires at the mains block, the transformer
and the AC terminals on the PCB
Check the mains block is connected correctly; live to live
(brown), neutral to neutral (blue)
No Power to unit (battery only)
Don't forget to press the battery kick-start button
Check the battery fuse F2 and replace if blown
Check for loose wires at the BATT terminals on the PCB
Check that the battery wires are connected correctly; red
from BATT+ to the battery positive (+), black from BATT-
to the battery negative (-)
Heartbeat LED is not flashing
Remove ALL power (AC Mains and Battery) and then
reapply power again
Network Data LED's are not flashing
Remove ALL power (AC Mains and Battery) and remove
ALL
wires
from
re-apply power again before referring to the Network
Diagnostics table on page 13
Keypads
Keypad does not operate
Check that the keypad is wired correctly from the control
panel (see page 13 for wiring details)
Check the network fuses F3 and F5 and replace if blown
Use the network diagnostics (see page 13 for details)
Keypad does not accept codes
If the system has more than one keypad check that each
keypad is addressed differently, see page 15 for details
If the keypad is on a long cable run, check the voltage
between the '+' and '–' terminals at the keypad and
ensure that it measures no less than 10.0V
Check that you are using the correct User codes. The
default Engineer code is
default Master User code is
Check that the User code you are using is not 'Time
Locked', if the User code is time locked then the access
code will only be accepted when the Control Timer is off
(see pages 52 and 88 for details)
Keypad zones do not operate
Each keypad zone has to be mapped onto the system
before it can be used (see page 57 for details)
The zone is not programmed (see page 34 for details)
Keypad emergency keys do not operate
Each keypad can be configured so that the emergency
keys PA, FIRE and MEDICAL can be enabled or
disabled. Check that the keypad has been programmed
correctly (see page 57 for details)
Premier 640 Installation Manual
the
network
terminals.
!"#$
'()*+
Then
and the
INS344

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents