Texecom Premier 640 Installation Manual page 64

Hide thumbs Also See for Premier 640:
Table of Contents

Advertisement

Programming the Control Panel
23 - Part Armed
This output type activates when the selected area is part armed
and deactivates when the selected area is disarmed.
24 - Part Arming
This output type activates when the selected area is part
arming and deactivates when the selected area arms.
25 - Force Armable
This output type activates when the selected area has at least
one zone with the 'Force Omit' attribute, and the area is able
to be force armed. It will deactivate when the area cannot be
force armed.
26 - Force Armed
This output type activates when the selected area is forced to
arm with zones active, and deactivates when the all zones are
reinstated.
27 - Arm Failed
This output type activates when the selected area fails to arm
because a zone is in fault, and deactivates when a valid User
code is entered.
28 - Bell SAB
This output type activates when an External alarm occurs in the
selected area, and deactivates when area is disarmed or the
'Bell Duration' timer expires.
29 - Bell SCB
This output type deactivates when an External alarm occurs in
the selected area, and activates when area is disarmed or the
'Bell Duration' timer expires.
30 - Strobe
This output type activates when an External alarm (or Arm Fail)
occurs in the selected area, and deactivates when area is
disarmed (or a valid User code is entered).
31 - Detector Latch
This output type activates for 5 seconds when the selected
area is in the exit mode then activates again when the area
arms and deactivates when an Intruder alarm occurs or the
selected area is disarmed.
32 - Detector Reset
This output type is normally active, and deactivates for 5
seconds when the selected area is in the exit mode.
33 - Walk Test Active
This output type activates when the 'Walk Test' procedure is
selected, and deactivates when the 'Walk Test' procedure is
cancelled.
34 - Zones Omitted
This output type activates when a zone in the selected area
with the 'Omit' attribute, is omitted by the user, and
deactivates when the zone is reinstated.
35 - 24Hr Zones Omit
This output type activates when a zone programmed as '24Hr
Audible' or '24Hr Silent' (with the 'Omit' attribute) is omitted by
the user, and deactivates when the zone is reinstated.
36 - Reset Required
This output type activates when the selected area requires a
reset following an alarm, and deactivates when the alarm is
reset.
37 - Door Strike
This output type activates for the 4 seconds when a User code
with the 'Door Strike' attribute is entered for the selected area.
38 - Chime Mimic
This output type activates for 2 seconds when a zone in the
selected area with the 'Chime' attribute is activated.
64
39 - Chime Enabled
This output type activates when 'Chime' is enabled for the
selected area, and deactivates when 'Chime' is disabled for
the selected area.
40 - DK First Knock
This output type activates when a zone in the selected area
with the 'Double Knock' attribute is activated for the first time,
and deactivates when the zone causes an alarm or the
'Double Knock Delay' timer expires.
41 - BP First Knock
This output type activates when a zone in the selected area
with the 'Beam Pair' attribute is activated for the first time and
deactivates when another zone with the 'Beam Pair' attribute,
causes an alarm or the 'Beam Pair Time' expires.
42 - On Test
This output type activates when a zone in the selected area
with the 'Test' attribute is placed on test and deactivates when
the 'Soak Test Time' expires.
43 - Test Fail
This output type activates when a zone in the selected area with
the 'Test' attribute is placed on test (and fails) and deactivates
when an Engineer code is entered or the 'Soak Test Time' expires.
44 - Internal Alarm
This output type activates when an Internal alarm occurs in the
selected area, and deactivates when the alarm is cancelled.
45 - Auto Arming
This output type activates when the selected area 'Auto
Arms', and deactivates when the selected area is disarmed.
46 - Time Arming
This output type activates for 5 minutes prior to the selected
area being armed using the 'Control Timers'.
47 - 1
st
Code Entered
This output type activates for 30 seconds when a User code
with the 'Dual Code' attribute is entered for the selected area.
48 - 2
nd
Code Entered
This output type activates for 30 seconds when two User
codes with the 'Dual Code' attribute are entered for the
selected area.
49 - Area Secured
This output type activates whenever a 'Security Key' zone
type is used to lock keypads out and deactivates when the
keypads are unlocked again.
50 - Part Armed 1
This output type activates when a Part Arm 1 is selected for
the selected area and deactivates when part arm 1 is
disarmed.
51 - Part Armed 2
This output type activates when a Part Arm 2 is selected for
the selected area and deactivates when part arm 2 is
disarmed.
52 - Part Armed 3
This output type activates when a Part Arm 3 is selected for
the selected area and deactivates when part arm 3 is
disarmed.
53 - Custom Alarm
This output type activates when any 'Custom' zone type
causes an alarm in the selected area and deactivates when a
valid user code is entered.
Premier 640 Installation Manual
INS344