Premier 640 Installation Manual

5.2. Area Programming

Timers

YES to Select:-
Area Programming
Yes
Area Programming
Timers
Yes
A1> Exit Delay
030 Second(s)
A2> Exit Delay
030 Second(s)
Area
B2> Exit Delay
030 Second(s)
Yes
B2> Entry 1 Delay
020 Second(s)
???
B2> Entry 1 Delay
>025 Second(s)
Yes
These groups of 'Area' timers control timing and delay
functions for areas A1 – H8. Each timer can be programmed
for any value between 000 and 999.
INS344
Use the SCROLL key to
select an area
Use the AREA key to
Jump a block of 8 areas
(A2-B2, C1-D1 etc)
P ress YES to move to
the required timer group
or press RESET to move
backwards e.g. YES
Enter a new timer value
e.g. 025 = 25 Seconds
1 - Exit Delay- for Areas A1 to H8
When the area exit mode is programmed as 'Timed' this timer
controls the delay between the user initiating the exit mode
for the selected area and the area actually.
2 - Entry 1 Delay - for Areas A1 to H8
If the area is armed and an 'Entry/Exit 1' zone is activated,
this timer will start and the entry tone will be heard. If the area
is not disarmed before this timer expires, the '2
timer will start.
3 - Entry 2 Delay - for Areas A1 to H8
If the area is armed and an 'Entry/Exit 2' zone is activated,
this timer will start and the entry tone will be heard. If the area
is not disarmed before this timer expires, the '2
timer will start.
4 - 2
nd
Entry Dly - for Areas A1 to H8
When the area 'Entry Delay 1 or 2' timer expires, this timer will
start and an Internal alarm will occur. If the area is still not
disarmed before this timer expires, an Intruder alarm will then
occur.
5 - Bell Delay - for Areas A1 to H8
This timer controls the delay between an Intruder alarm
occurring in the selected area and the 'Bell/Strobe' output
activating.
6 - Bell Duration - for Areas A1 to H8
This timer controls the duration of the 'Bell' output after an
Intruder alarm has occurred in the selected area and any
programmed 'Bell Delay' has expired.
7 - Coms Delay. for Areas A1 to H8
This timer controls the delay between an Intruder alarm
occurring in the selected area and the communicator reporting to
the Alarm Receiving Centre.
8 - Part Bell Dly. for Areas A1 to H8
When the selected area is 'Part Armed' this timer controls the
delay between an Intruder alarm occurring in the selected
area and the 'Bell/Strobe' output activating, the internal
sounders will also sound during this time as a warning.
Programming the Control Panel
nd
Entry Delay'
nd
Entry Delay'
39