Appendix 1 System Technical Parameters - Emerson ACTURA Flex 48330 User Manual

Power system
Table of Contents

Advertisement

Appendix 1 System Technical Parameters

Parameter
AC input over-voltage
alarm point
AC input over-voltage
recovery point
AC input alarm and
protection
AC input under-voltage
alarm point
AC input under-voltage
recovery point
DC output over-voltage
protection point
DC output over-voltage
alarm point
DC output over-voltage
recovery point
DC output under-voltage
alarm point
DC output alarm and
DC output under-voltage
protection
recovery point
LLVD
BLVD
Output delay
Fan speed adjustable
CS
RS
EMC
Immunity to EFT
Immunity to ESD
Immunity to Surges
Lightning protection
At AC side
features
Acoustic noise
Others
Insulation resistance
category
Default: 280 ! 5Vac, cofigurable through monitoring module
Default: 270 ! 5Vac, 10Vac lower than the AC input
over-voltage alarm point
Default: 180 ! 5Vac, configurable through monitoring module
Default: 190 ! 5Vac, 10Vac higher than the AC input
under-voltage alarm point
Default: 59.0 ! 0.2Vdc
Default: 58.5 ! 0.2Vdc, configurable through monitoring
module
Default: 58 ! 0.2Vdc, 0.5Vdc lower than the over-voltage
alarm point
Default: 45.0 ! 0.2Vdc, configurable through monitoring
module
Default: 45.5 ! 0.2Vdc, 0.5Vdc higher than the under-voltage
alarm point
Default: 44 ! 0.2Vdc, configurable through monitoring module
Default: 43.2 ! 0.2Vdc, configurable through monitoring
module
Output voltage can rise slowly upon rectifier start up. The rise
time is configurable
Rectifier fan speed can be set to half or full speed.
EN300386 2001, Class A
EN61000-4-4, Level 3
Air discharge: 8kV. Contact discharge: 4kV. EN61000-4-2
EN61000-4-5, Level 4
The AC input side can withstand 10/700μs simulated
lightning voltage 5kV for ! 5 times, or 8/20μs simulated
lightning surge current 20kA for ! 5 times, or 8/20μs
simulated lightning surge current 40kA once. The test interval
is not smaller than 1 minute.
55dB (A)
At temperature of 15°C ~ 35°C and relative humidity not
higher than 90%RH, apply a test voltage of 500Vdc. The
insulation resistances between AC circuit and earth, between
DC circuit and earth, or between AC and DC circuits are no
less than 10M Ω
ACTURA Flex 48330 Power System User Manual
Appendix 1 System Technical Parameters
Note
77