Table 5-12 Charging Management Parameter Value Description; Figure 5-2 Bc/Fc Switchover Diagram - Emerson ACTURA Flex 48330 User Manual

Power system
Table of Contents

Advertisement

Parameter
Float
42V ~ 58V
Boost
Limit (current
0.1 ~ 0.25C
limit)
Over (over current
0.3C
point)
Automatic Boost
Yes, No
Cyclic Boost
Cyclic Boost
48 ~ 8760h
Interval
Cyclic Boost Time 30 ~ 2880min
To Boost Current
0.50 ~ 0.80C
To Boost
0.1 ~ 0.95
Capacity
Constant BC Curr 0.02 ~ 0.99C10 0.01C
Duration (of
30 ~ 1440min
constant BC)
Boost Limit
60 ~ 2880min
3. The BC/FC switchover diagram is shown below:

Table 5-12 Charging management parameter value description

Range
Default
In the FC state, all rectifiers output
53.5V
voltage according to the set "Float"
In the BC state, all rectifiers output
56.4V
voltage according to the set "Boost"
When the monitoring module detects that the battery charging
current is higher than the "Limit", it will control the current of the
0.1C
rectifiers, through which it can limit the battery charging current.
10
10
C
rated capacity of one battery string.
When the monitoring module detects that the battery charging
~ 1.0C
0.300C
current is higher than the "Over", it will raise the battery charge
10
10
10
over-current alarm.
Select "Y", and BC will be conducted when conditions allow
Y
Select "Y", and the monitoring module will control the system to
enter the Cyclic Boost when the FC time reaches the "Cyclic Boost
2400h
Interval". The battery charging voltage is the preset "Boost", and
the time is the preset "Cyclic Boost Time"
720min
0.06C
The monitoring module will control the system enter the BC state
10
10
when the battery capacity decreases to the value of "To Boost
Capacity", or when the charge current reaches the "To Boost
0.80
Current". The charge voltage will be the "Boost".
The system in the BC state will enter the FC state when the charge
10
current decreases to the "Constant BC Curr" and after the
180min
"Duration". The battery charge voltage then will be the "Float".
To ensure safety, the monitoring module will forcefully control the
system to enter the FC state if during the BC state, the BC time
1080min
reaches the "Boost Limit", or abnormalities occur (such as AC
failure and battery route faulty, etc.).
FC

Figure 5-2 BC/FC switchover diagram

ACTURA Flex 48330 Power System User Manual
Value description
is the battery rated capacity, generally set to 10 ~ 20% of the
10
FC time longer than "Scheduled BC Interval"
Battery charge current
bigger than "To BC Current"
Battery capacity smaller
than "To BC Capacity"
Constant BC
time-up
Constant
BC
BC time longer than
"BC LVD Time"
Abnormal situation
Chapter 5 Operating SCU
The "Boost" must be
higher than the "Float"
BC
Charge current
smaller than
"Constant BC
Curr"
59