Chapter 5 Operating SCU
3. Use "
press "ENT" to confirm.
If there is no historical alarm, the prompt will be "Alarm History: None".
The historical alarms of the monitoring module are stored in cyclic order. Up to 200
alarms will be recorded. Above that, the earliest alarm will be cleared automatically.
At the monitoring module, the displayed historical alarm information includes: alarm
serial No., alarm name and alarm start/end time (year, month, day, hour, minute,
second).
If it is a rectifier that raised the alarm, the ID of that rectifier will be displayed.
4. At any Alarm History information page, press "ESC" repeatedly to return to the
higher-level menus.
Status
Rectifiers
Active Alarm
Alarm History
" or "
" to select the "Alarm History", as shown in the above figure and
ALARM HISTORY
None
1Alarm
SPD Fault
040411 20:08:30
040411 22:08:30
ACTURA Flex 48330 Power System User Manual