Emerson ACTURA Flex 48330 User Manual page 88

Power system
Table of Contents

Advertisement

78
Appendix 1 System Technical Parameters
Parameter
Others
Mechanica
category
Dielectric strength
MTBF
Size (mm)
Weight
ACTURA Flex 48330 Power System User Manual
(Remove the SPD, monitoring module and rectifiers from the
system before the test.)
AC to DC circuits, AC circuit to earth: 50Hz, 3,000Vac (RMS).
DC circuit to earth: 50Hz, 1,000Vac (RMS).
Assistant circuit (not directly connected to the host circuit):
50Hz, 500Vac (RMS).
For all the three tests above, there should be no breakdown
or flashover within 1min, with leakage current not bigger than
10mA.
250,000hr
600 (W) % 600 (D)
600 (W) % 400
% 2000 (H)
(D) % 2000 (H)
<135kg (without
<125kg (without
rectifiers)
rectifiers)
Note
600 (W) % 400 (D)
% 700 (H)
<60kg (without
rectifiers)