5.7.4 Charging Management Parameters

1. There are 6 related pages, as shown below:
LLVD Enable: Y
BLVD Enable: Y
LVD Mode:
Voltage
LVD Vlotage
LLVD:
BLVD:
LVD Time
LLVD:
BLVD:
" or "
" to select one page or one of the parameters, and "

Table 5-11 Value description of the LVD parameters

Default
Select "Y" to enable LLVD function
Y
Select "Y" to disable the BLVD function
Select "Voltage", when the monitoring module detects that the battery
Voltage
voltage is lower than the prestet "LLVD Volt", the load will be
disconnected, and so is the battery when the battery voltage is lower
44.0V
than the preset 'BLVD Volt".
43.2V
Select "Time", when the discharge time reaches the preset "LLVD Time",
300min
the monitoring module will disconnect the load; when the discharge time
600min
reaches the preset "BLVD Time", it will disconnect the battery
Float:
Boost:
Limit: 0.100C10
Over: 0.300c10
ACTURA Flex 48330 Power System User Manual
Chapter 5 Operating SCU
44.0
43.2
300min
600min
Value description
53.5
56.4
57