Unpacking - Emerson ACTURA Flex 48330 User Manual

Power system
Table of Contents

Advertisement

14
Chapter 2 Installation
In this formula: A is the sectional area of the lead (mm
flowing through the lead, L is the length (m) of the lead loop, △U is the permitted
voltage drop on the lead, while K is the conductivity. Kcopper=57. For safety, the
voltage drop on the cables connecting battery and load cannot exceed 3.2V.
The sectional area of the lightning protection earth cable should not be less than
2
6mm
determined by user. Take the greatest sectional area among the above 3 earth
cables as that of the cable connecting the user earth bar.
3. Purchase materials according to the materials list and inspect the materials, for
example, check the heat durability, moisture resistance, flame resistance, and
voltage resistance of the cable.
4. The auxiliary materials for power supply installation include expansive bolts,
binding strips, and insulating tape.

2.1.5 Unpacking

To ensure smooth installation, the power equipment must be carefully inspected
when it is unpacked.
The equipment unpacking and inspection are allowed only after it arrives the
installation site. The inspection is co-accomplished by the user representative and
representative from Emerson Network Power Co., Ltd.
When inspecting the equipment, first open the packing case with packing list put in
it, take out the packing list, and conduct inspection against the packing label,
including the customer name, customer address, machine No., total amount, case
No., contract No., etc.
Unpacking and inspection: after opening the packing case, check the goods one by
one according to the goods list on the packing label. The checking should include:
1. The number and serial number marked on the packing cases according to the
actual number of the packing cases.
2. The correctness of the equipment packing according to the packing list.
3. The number and model of the accessories according to the accessory list.
4. The completeness of the equipment set according to the system configuration.
5. The condition of the goods through visual inspection. For example, check if the
cabinet is damaged, if the cabinet has regained moisture; shake gently the rectifiers
and monitoring module to see if the parts and connections have been loosened
during delivery.
, and that of the DC operation earth cable, usually between 35-50mm
ACTURA Flex 48330 Power System User Manual
2
), ΣI is the total current (A)
2
, is

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents