Emerson ACTURA Flex 48330 User Manual page 55

Power system
Table of Contents

Advertisement

Serial
Alarm
No.
36
Batt4 Failure
37
Batt1 Over-curr
38
Batt2 Over-curr
39
Rect Vac Err
40
Rect Over Temp
41
Rect Failure
42
Rect Protect
43
Rect Fan Fails
44
Rect PowerLimit
45
Rect Com Failure
46
Multi Rect Fail
47
Self-detect error
48
Manual Mode
49
Non-FC Status
50
Batt Discharge
51
Curr Imbalance
52
Batt Test Error
53
Short Test Fault
54
Outvolt Fault
55
System Maintain
56
Alarm Block
Description
Over-load, short circuit, manual
disconnection or alarm circuit faulty
The charge current of battery group 1
is bigger than the set value of
parameter "Over"
The charge current of battery group 2
is bigger than the set value of
parameter "Over"
All AC voltages are lower than the
AC low-volt point
Rectifier internal temperature higher
than 90°C
Rectifier over-voltage, higher than
rectifier high threshold
AC over-voltage ( ƒ 295V) or
under-voltage ( 80V)
Fan faulty
AC voltage lower than 176V, with
rectifier internal higher than 85°C or
temperature at inlet higher than 45°C
Rectifier and monitoring module
communication interrupted
More than 2 rectifiers raised alarms
Error is detected through hardware
self-detection
Battery management in the manual
state
Including auto-BC, Cyclic Boost,
constant current test and short test
Battery being discharging
In a system with load shunt, the
detected load current plus battery
current differs sharply from the
rectifier output current
Battery discharge time unexpectedly
short
During the short test, the two
batteries discharged more than the
set value
The maintenance FC voltage
different from the busbar voltage, or
the reported data. The difference is
more than 1V
The pre-set system maintenance
time is due
Alarms sent to the host are blocked,
valid in EEM-M protocol
ACTURA Flex 48330 Power System User Manual
Chapter 5 Operating SCU
Default
Default
related
alarm level
relay
Critical
None
Observation
None
Observation
None
Major
3
Observation
None
Critical
3
Observation
3
Major
3
Observation
3
Major
3
Critical
None
No alarm
None
No alarm
None
No alarm
7
No alarm
None
Not existent in this
No alarm
None
power system series
Observation
None
Observation
None
Observation
None
Observation
None
No alarm
None
45
Related parameter
configuration

Hide quick links: