Table 5-18 Value Description Of System Settings - Emerson ACTURA Flex 48330 User Manual

Power system
Table of Contents

Advertisement

68
Chapter 5 Operating SCU
Parameter
Text
Address
CommMode
BaudRate
When
CallBack
"CommMode
Num.
" is set to
CallBack
"MODEM" or
Number
"EEM-M"
Set Date
Set Time
Initialize
password
Operator
Init Param
level or
(Initialize
above
parameter
s)

Table 5-18 Value description of system settings

Range
Chinese, English and
Spanish
1 ~ 254
modem, EEM-M,
RS-232
1200bps, 2400bps,
4800bps, 9600bps
1 ~ 10
19 digits at most
2,000 ~ 2,099
Hour, min, sec
Y, N
Y, N
ACTURA Flex 48330 Power System User Manual
Default
Chinese Set according to your need
The addresses of power systems that are at the
same monitored office should be different
"MODEM": Through modem and based on the
Telecom protocol.
"EEM-M": Through modem and based on the EES
protocol.
"RS-232": Through a transparent serial port and
based on the Telecom protocol
Make sure the baud rates of both the sending and
receiving parties are the same
Set according to the actual need. In a extension
3
system, sometimes you need to put a "," between the
main number and extension number. When the
callback number is less than 19 digits, end it with a
"#"
Set the time according to the current actual time,
regardless of whether it is a leap year or not
Selecting "Y" can reset the user level and
N
administrator level passwords to the defaults
When the system parameters cannot be set normally,
and the usual resetting methods do not work, you
can set the "Init Param" to Y, and all the system
N
parameters will be restored to defaults. Alarms may
be raised for the defaults may fail to meet the actual
situation. Set the parameters according to the actual
situation then.
Value description